6.10
Switchover between different settings
Overview
There are applications that require different converter settings.
Example:
Different motors are operated on one converter. The converter must operate with the motor
data of the particular motor and the appropriate ramp-function generator.
Function description
Drive Data Sets (DDS)
Some converter functions can be set differently, and there can be a switch between the different
settings.
Note
You can only switch over the motor data of the drive data sets in the "ready for operation" state
with the motor switched off. The switchover time is approx. 50 ms.
If you do not switch over the motor data together with the drive data sets (i.e. same motor
number in p0826), then the drive data sets can also be switched over in operation.
The associated parameters are indexed (index 0, 1, 2, or 3). One of the four indexes is selected
with control commands, and thereby one of the four saved settings.
The settings in the converter with the same index are called a drive data set.
0
6HWSRLQWSURFHVVLQJ
0RWRUFRQWURO
6HWSRLQWV
IL[HGVHWSRLQWV
PRWRUL]HGSRWHQWLRPHWHU
MRJJLQJ
HQHUJ\VDYLQJPRGH
IO\LQJUHVWDUW
FDVFDGHFRQWURO
$GGLWLRQDOIXQFWLRQV
RYHUFXUUHQW
RYHUYROWDJH
RYHUWHPSHUDWXUH
ORDGPRQLWRULQJ
3URWHFWLRQ
''6
''6
''6
''6
Advanced commissioning
6.10 Switchover between different settings
SINAMICS G120XA converter
346
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......