p1967
Speed_ctrl_opt dynamic factor / n_opt dyn_factor
Access level: 3
Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
1 [%]
Max:
400 [%]
Factory setting:
100 [%]
Description:
Sets the dynamic response factor for speed controller optimization.
After optimization, the dynamic response achieved is displayed in r1968.
Dependency:
See also: p1959, r1968
See also: F07985
Note
For a rotating measurement, this parameter can be used to optimize the speed controller.
p1967 = 100 % --> speed controller optimization according to a symmetric optimum.
p1967 > 100 % --> optimization with a higher dynamic response (Kp higher, Tn lower).
If the actual dynamic response (see r1968) is significantly reduced with respect to the required dynamic response
(p1967), then this can be as a result of mechanical load oscillations. If, in spite of this load behavior, a higher dynamic
response is required, then the oscillation test (p1959.4 = 0) should be deactivated and the measurement repeated.
r1968
Speed_ctrl_opt dynamic factor actual / n_opt dyn_fact act
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description:
Displays the dynamic factor which is actually achieved for the vibration test
Dependency:
See also: p1959, p1967
See also: F07985
Note
This dynamic factor only refers to the control mode of the speed controller set in p1960.
p1980[0...n]
PolID technique / PolID technique
Access level: 3
Calculated: CALC_MOD_REG Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: MDS, p0130
Unit group: -
Unit selection: -
Function diagram: -
Min:
1
Max:
10
Factory setting:
4
Description:
Sets the pole position identification technique.
p1980 = 1, 8: The current magnitude is set using p0329.
p1980 = 4, 6: The current magnitude of the first measurement section is set using p0325, the second using p0329.
p1980 = 10: The rated motor current is impressed to align.
The current magnitudes are limited to the rated power unit values.
Value:
1:
Voltage pulsing 1st harmonics
4:
Voltage pulsing 2-stage
6:
Voltage pulsing 2-stage inverse
8:
Voltage pulsing 2nd harmonic, inverse
10:
DC current injection
Dependency:
See also: p1780
See also: F07969
Parameters
7.3 Parameters
SINAMICS G120XA converter
550
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......