p29527
Multi-pump control interlocking time / Mpc t_interl
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0 [s]
Max:
650 [s]
Factory setting:
0 [s]
Description:
Interlocking time during which, following the connection or disconnection of a motor, no further motors are connected
or disconnected using the multi-control control. This avoids duplicate switching operations.
p29528
Multi-pump control switch-out speed offset / Mpc sw_out offset
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: 3_1
Unit selection: p0505
Function diagram: -
Min:
0.0 [rpm]
Max:
21000.0 [rpm]
Factory setting:
100.0 [rpm]
Description:
Sets the speed offset which pluses p1080 as the speed threshold.
If the system deviation of the technology controller has exceeded the threshold p29523 for p29525s (or exceeded the
threshold p29526) and the motor has reached the speed threshold p1080+p29528, a motor will be switched out.
r29529.0...7
CO/BO: Multi-pump control status word / Mpc ZSW
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the status word of the multi-pump control
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Start motor 1
Yes
No
-
01
Start motor 2
Yes
No
-
02
Start motor 3
Yes
No
-
03
Start motor 4
Yes
No
-
04
Switch-in/switch-out active
Yes
No
-
05
All motors active
Yes
No
-
06
Cycling not possible
Yes
No
-
07
Alarm active
Yes
No
-
p29530[0...3]
Multi-pump control absolute operating hours / Mpc op_hrs
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00 [h]
Max:
340.28235E36 [h]
Factory setting:
0.00 [h]
Description:
Displays the total operating hours for motors.
The display can only be reset to zero.
Index:
[0] = motor 1 operating hours
[1] = motor 2 operating hours
[2] = motor 3 operating hours
[3] = motor 4 operating hours
Parameters
7.3 Parameters
SINAMICS G120XA converter
708
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......