6.9.2
Bypass
Overview
The "Bypass" function switches the motor between converter and line operation.
.
.
.
.
.
'212
'2&20
'212
'2&20
',
',
9287
*1'
.
.
.
U
%,S>@
U
%,S>@
S
U
S
U
Figure 6-84
Bypass control via converter
Requirements placed on the K1 converter contactor and K2 line contactor:
● K1 and K2 are designed for switching under load.
● K2 is designed for switching an inductive load.
● K1 and K2 are interlocked against closing at the same time.
Requirements
● The "Bypass" function is supported only for induction motors.
● The "Flying restart" function must be activated for the "Bypass" function (p1200 = 1 or 4).
Flying restart – switching on while the motor is running (Page 318)
$
%
&
Advanced commissioning
6.9 Energy saving
SINAMICS G120XA converter
332
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB