r4047
PM330 digital outputs status / PM330 DO status
CUG120XA_USS
(PM330)
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the status of the digital outputs of Power Module 330 (PM330).
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DO 0 (X9.8: enable signal UDC link charged)
High
Low
-
01
DO 1 (X9.11/X9.12: main contactor control)
High
Low
-
Note
DO: Digital Output
p4095
PM330 digital inputs simulation mode / PM330 DI sim_mode
CUG120XA_USS
(PM330)
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 bin
Description:
Sets the simulation mode for digital inputs of the PM330 power unit.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DI 0 (X9.3, external alarm)
Simulation
Terminal eval
-
01
DI 1 (X9.4, external fault)
Simulation
Terminal eval
-
02
DI 2 (X9.5, Emergency Off category 0)
Simulation
Terminal eval
-
03
DI 3 (X9.6, Emergency Off category 1)
Simulation
Terminal eval
-
Dependency:
The setpoint for the input signals is specified using p4096.
See also: p4096
Note
This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
p4096
PM330 digital inputs simulation mode setpoint / PM330 DI sim setp
CUG120XA_USS
(PM330)
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2275
Min:
-
Max:
-
Factory setting:
0000 bin
Description:
Sets the setpoint for the input signals in the digital input simulation mode of the PM330 power unit.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DI 0 (X9.3, external alarm)
High
Low
-
01
DI 1 (X9.4, external fault)
High
Low
-
02
DI 2 (X9.5, Emergency Off category 0)
High
Low
-
03
DI 3 (X9.6, Emergency Off category 1)
High
Low
-
Dependency:
The simulation of a digital input is selected using p4095.
See also: p4095
Note
This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
661
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......