![Siemens SINAMICS G120XA Скачать руководство пользователя страница 261](http://html.mh-extra.com/html/siemens/sinamics-g120xa/sinamics-g120xa_operating-instructions-manual_381566261.webp)
$FWXDOYDOXH
)LOOLQJOHYHOVHWSRLQW
6SHHGVHWSRLQW
W
S
S
W
Figure 6-47
Example for speed setpoint and actual process value for autotuning
The converter calculates the parameters of the PID controller from the determined oscillation
frequency.
Executing autotuning
1. Select with p2350 the appropriate controller setting.
2. Switch on the motor.
The converter signals Alarm A07444.
3. Wait until alarm A07444 goes away.
The converter has recalculated parameters p2280, p2274 and p2285.
If the converter signals fault F07445:
– If possible, double p2354 and p2355.
– Repeat the autotuning with the changed parameters.
4. Back up the calculated values so that they are protected against power failure, e.g. using the
BOP‑2: OPTIONS → RAM‑ROM.
You have auto tuned the PID controller.
❒
Parameters
Number
Name
Factory setting
p2274
Technology controller differentiation time constant
0.0 s
p2280
Technology controller proportional gain
See parameter list
p2285
Technology controller integral time
See parameter list
Advanced commissioning
6.5 Technology controller
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
259
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......