Configuring the control stages
21040012
49
10.
Enter the name (maximum 13 characters) for this stage. For more information, read
on page 17. To save the name, press
ENTER
until the cursor returns to the
beginning of the line. To cancel the change, press
BACK
.
11.
Repeat steps 2 to 10 for each variable stage you have connected to the Supra.
12.
Press
BACK
to return to the Main Menu.
Configuring relays for actuators
You can connect up to two actuators to a Supra. Each actuator you connect requires two relays: one
for extending the actuator arm (opening the inlet), and one for retracting the arm (closing the inlet).
You can connect actuators to any of the available relays, but side-by-side relays are recommended.
Before configuring the actuator relays, you need to know the following.
The open relay number
The close relay number
The feedback terminal to which the actuator is connected (FB1 for Act 1 and FB2 for Act 2)
Whether or not the actuator closes during tunnel mode
The zone in which the actuator is located
on page 125 when configuring relays.
DO NOT switch on power to the actuator until you have completed the following
steps. Switching on the power to the actuator before completing these steps can
damage the actuator or actuator power supply and will burn out the relays.
To configure relays for actuators
These steps use Actuator 1. If you are configuring a second actuator, follow the
same steps using Actuator 2 in place of Actuator 1.
If you are configuring the actuator to close during tunnel mode, configure both
the open and close relays.
1.
From the Main Menu, select
Configuration
(5).
2.
Scroll to the relay you want to configure for opening the actuator.
The display should look like the following example.