Performing diagnostic tests
21040012
107
This is the total water usage for the current day (12:00 AM until current time)
6.
Press
BACK
twice to return to the Main Menu.
Monitoring power conditions
If you get several low or high power alarms, you should look at the incoming power supply. The
information in the power tests can help you determine if you have power supply problems.
To monitor power conditions
1.
From the Main Menu, select
Diagnostics
(6).
2.
From the Diagnostics menu, select
Power Supply
(2).
The display should look like the following example.
3.
Check the value next to
Now
; it indicates the condition of the power the Supra is receiving. If
the value is not within approximately ±3 Hz of your power frequency, or the voltage outside of
the 10 to 18 VDC range, an alarm will sound.
The
Min
and
Max
values indicate the lowest and highest values the Supra received since the
Supra was powered up or since you cleared the values.
4.
Press
BACK
.
The display should look like the following example.
5.
If you want to clear the values, press
ENTER
.
6.
Press
BACK
until you return to the Main Menu.
Water
400 Gal
Pulses
40
POWER SUPPLY
Min 14.4 VDC 59.5 Hz
Now 15.4 VDC 60.0 Hz
Max 16.1 VDC 60.4 Hz
Press ENTER to clear
values or press BACK
to keep old values