Configuring the control stages
21040012
53
Configuring relays for heating, cooling, or temperature-based
duty cycles
Relays configured for heating can control equipment such as electric or gas heaters that can be either
ON or OFF. The relays switch on when the temperature drops below the
set point
and off when it
rises above.
Relays configured for cooling can control single-speed fans, misters, or other cooling equipment that
can be either ON or OFF. The relays switch on when the temperature rises above the
set point
and
off when it drops below.
This section is for relays. For information about variable-powered heating and
If you need to connect more cooling elements than you have relays, and you are
not using all the variable stages, you can use any available variable stages as
ON/OFF stages. For more information, read
on page 125 when configuring relays.
To configure relays for heating, cooling, or temperature-based duty cycles
1.
From the Main Menu, select
Configuration
(5).
2.
Scroll to the relay you want to configure.
The display should look like the following example.
3.
To change the zone the element will be controlling, place the cursor on the Zone line and then
press
ENTER
. Press
+
or
–
to change the zone and then press
ENTER
.
4.
Scroll to the Mode line and then press
ENTER
.
5.
To configure the relay for controlling a heating element, press
+
or
–
until you see
Heat
and
then press
ENTER
. To configure the relay for controlling a cooling element, press
+
or
–
until
you see
Cool
and then press
ENTER
.
6.
Scroll to
Tunnel turn off
and then press
ENTER
.
7.
Press
+
or
–
to select
Yes
(off during tunnel mode) or
No
(can be on during tunnel mode)
and then press
ENTER
.
Zone
Mode
Tunnel option (
yes
is enabled;
no
is not enabled)
Name
_Relay 1 Zone 1
Unassigned
Tunnel turn off? No
Name: Rly 01