Appendix F: Settings worksheets
21040012
133
Variable stage settings worksheet
Setting
Variable 1
Variable 2
Variable 3
Variable 4
Type of element
Heat Cool
Heat Cool
Heat Cool
Heat Cool
On full at
Idle at/Setpoint
Off at
Idle speed/Min heat
Temperature in °F/°C, range:
–
10 to 43°C, 14 to 110°F
Idle speed or Min heat in %, range: 0 to 100 %
If you need to connect more heating or cooling elements than you have relays,
and you are not using all the variable stages, you can use any available variable
stage as an ON/OFF stage.
Set the
idle speed
(
min heat
for a heating stage) to 100% and
off at
to the
temperature at which you want the stage to switch on/off. For more information,
Temperature setback worksheet
Temperature setback automatically changes the temperature
set point
for a specific period of time
during the day. Temperature setback works for both
group set points
and
growth curves
.
There are two separate “setback groups”: A and B. For more information, read
Item
Setback A setting
Setback B setting
Example
Zone
1 2 3 4 All
1 2 3 4 All
1 2 3 4 All
Status
Enabled Disabled
Enabled Disabled
Enabled Disabled
Setback
°C °F
°C °F
8.0
°C °F
Start Time
:
AM PM
:
AM PM
06
:
00
AM PM
Stop Time
:
AM PM
:
AM PM
10
:
00
AM PM
Setback range: 1.0 to 25°F (0.6 to 13.9°C)