Configuring the control stages
21040012
51
Stage 1: To set the limit switches
1.
From the Main Menu, select
Maintenance
(2).
2.
From the Maintenance menu, select
Calibrate Actuator
(2).
The display should look like the following example.
3.
Scroll to
Set limit switches
and then press
ENTER
.
The display should look like the following example.
4.
Press
+
to extend (open) or
–
to retract (close) the inlets.
If the inlets DO NOT move in the proper direction, in other words, if they open when you
press
–
and close when you press
+
, the wiring for the relays is reversed. Correct the wiring
before repeating the test. For more information, read
If the inlets move in the proper direction, continue the test.
5.
Press
–
and then wait until the inlet reaches its fully closed position. Immediately after it reaches
the fully closed position, press
ENTER
.
6.
Set the limit switch for the fully closed position.
7.
Press
+
and then wait until the inlet reaches its fully open position. Immediately after it reaches
the fully open position, press
ENTER
.
8.
Set the limit switch for the fully open position.
9.
Press
–
and then wait until the inlet stops moving. If it does not stop in the proper position,
10.
Press
+
and then wait until the inlet stops moving. If it does not stop in the proper position,
11.
After the limit switches are set and the actuator operates properly, go to
Inlet 1
Never calibrated
Set limit switches
Calibrate now
Press + to open
Press - to close
Press ENTER to stop
Press Back when
done