Appendix F: Settings worksheets
134
Phason
Humidity compensation settings worksheet
If you have installed and configured a humidity sensor, you need to program the humidity
compensation. Programming the humidity compensation means setting the humidity factor and the
upper and lower humidity limits. For more information, read
If you are using Fahrenheit, a good guideline is to set the
humidity factor
equal to half
the cooling band. If you are using Celsius, use a value equal to the cooling band. For
example, if the temperature
set point
for the first stage is 70°F and the last stage
switches on at 78°F, the cooling band would be 8°F. You would set the
humidity
factor
to 4. For more information, see the following table.
Cooling band
(°C)
Cooling band
(°F)
Humidity factor
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
20.0
1
2
3
4
5
6
7
8
9
10
Setting
Notes
Humidity factor
A number from 0 to 10 used to calculated humidity compensation.
Upper limit
% 90% maximum, must be at least 20% higher than the lower limit.
Lower limit
% 30% minimum, must be at least 20% lower than the upper limit.