Programming the stages
21040012
81
4.
Enter the temperature using the numbers on the keypad, or press
+
or
–
to adjust the value and
then press
ENTER
.
The Supra interprets the last digit as a decimal. For example, to enter 40.0°F,
press 400.
5.
Scroll to
Minimum Pos
and then press
ENTER
.
6.
Enter the position the actuator will be at when the temperature reaches the
minimum set point
,
or press
+
or
–
to adjust the value and then press
ENTER
.
7.
Scroll down to the settings for the first stage and then press
ENTER
.
The display should look like the following example.
8.
Enter the stage’s
set point
, or press
+
or
–
to adjust the value and then press
ENTER
. Repeat this
step for the differential and position.
9.
Scroll down to the next stage and then press
ENTER
.
10.
Repeat steps 8 and 9 for each actuator stage.
11.
Press
BACK
twice to return to the Main Menu.
Programming curtain control relays
Curtains control the temperature by adjusting the airflow into the facility. Before setting up the
curtains, make sure you have properly configured the relays. For more information, read
Configuring relays for curtains
Programming the curtains means setting the temperature set point, idle band, and idle and run times.
Each curtain has six settings:
Set point – the temperature at which the curtain holds its position.
Idle band – the buffer around the set point within which the curtains hold their position.
Open run time – the duration the curtains open during the OPEN cycle
Open idle time – the duration the curtains hold their position during the OPEN cycle
Close run time – the duration the curtains open during the CLOSE cycle
Close idle time – the duration the curtains hold their position during the CLOSE cycle
Closes at
40.0°F
Minimum Pos
20%
1 83.4 - 84.9°F 40%
Set point
Stage
Differential
Position