Chapter 3: Configuration
48
Phason
Configuring variable stages means:
Selecting the zone (1, 2, 3, or 4) in which the stage will be controlling the equipment
Selecting whether the stage is a heating element (for example, a heat mat) or a cooling element
(for example, a fan)
For cooling elements only, selecting whether or not the stage reacts to tunnel mode
Assigning a name to the stage
For information about how variable stages work, see
Variable stage configuration worksheet
on page 126 when configuring
variable stages.
If you have a Variable DC Expansion Kit connected, configure the variable DC
outputs in the same way you configure variable stages. The variable DC outputs
display as
V1 (0-10V)
.
For more information about the expansion kit, read
To configure variable stages
1.
From the Main Menu, select
Configuration
(5).
2.
Scroll to the variable stage you want to configure.
The display should look like the following example.
3.
When the cursor is on the zone line, press
ENTER
.
4.
Press
+
or
–
to select the zone this stage will be controlling and then press
ENTER
.
5.
Scroll down to the Mode line and then press
ENTER
.
6.
Press
+
or
–
to select whether the stage is a heating, cooling, or unassigned stage and then press
ENTER
.
7.
Scroll to
Tunnel turn off
and then press
ENTER
.
8.
Press
+
or
–
to select
Yes
(off during tunnel mode) or
No
(can be on during tunnel mode)
and then press
ENTER
.
9.
Scroll to the Name line and then press
ENTER
.
Zone
Mode
Tunnel option (
yes
is enabled;
no
is not enabled)
Name
Var Stage 1 Zone 1
Cool
Tunnel turn off? No
VS Fan 1