Chapter 3: Configuration
52
Phason
Stage 2: To calibrate actuators
Calibrating actuators takes several minutes. You can stop the calibration process at
any time, but if you do, the Supra will not be able to properly control the inlets.
1.
From the Main Menu, select
Maintenance
(2).
2.
From the Maintenance menu, select
Calibrate Actuator
(2).
The display should look like the following example.
3.
Scroll to
Calibrate now
and then press
ENTER
.
If the actuator is operating properly, the inlet moves to its fully open position (100%), stops, and
then moves to its fully closed position (0%).
If the actuator stops after moving in the close direction, or if it fails to position
the inlet properly, the Supra is not receiving a proper feedback signal. This can
be incorrect wiring or a defective potentiometer. Correct this problem and then
restart the calibration at step 1. For more information read
, your actuator’s
If the calibration fails (for example, if the actuator jammed), the display shows
the reason for the failure. The date and time the actuator was last calibrated
does not change. Check the alarm messages and then look up the problem in
on page 117. Check the actuator itself. Fix any
mechanical or electrical problems.
4.
After the actuator has calibrated properly, press
BACK
to return to the list of actuators.
The display shows the date and time on which the actuator was calibrated.
5.
If you have a second actuator to calibrate, press
Down
until the second actuator is displayed and
6.
Press
BACK
twice to return to the Main Menu.
Inlet 1
Never calibrated
Calibrate now
Inlet 1
Last calibrated on:
7/6/2015 1:10 PM
Calibrate now