Chapter 2: Installation
32
Phason
To connect temperature probes
Connect the temperature probe as shown in the following diagram.
Do not run the probe cable in the same conduit as AC power cables
Do not run the sensor cable beside AC power cables or near electrical equipment.
When crossing other cables or power lines, cross them at a 90 degree angle.
Connecting a Relative Humidity Sensor
You can connect a Phason Relative Humidity Sensor (RHS) to the analog terminal. Connecting an
RHS allows you to monitor relative humidity in one of the Supra’s four zones.
You can monitor relative humidity with the Phason Relative Humidity Sensor (RHS
or RHS-P) only. Other humidity sensors will not work properly. For more
information about the RHS, see
Appendix D: Installation worksheet
on page 123 and
on page 125 when installing a Relative Humidity Sensor.