background image

 

TSBC Instruction Manual 

Page 1 of 48 

102059-01R3-3/20 

Thermal Solutions 

Boiler Control™ 

(TSBC™)

 

Instruction Manual 

 

 
 
    

 

 

Contents 

 
Introduction  
 Quick 

Reference 

 Overview 

Product Features 

 

 Boiler 

Sequence 

 

 

Single Boiler Control Mode 

 

 

Multiple Boiler Control Mode 

10 

 

EMS Boiler Control Mode 

 

11 

 

Manual Boiler Control Mode 

 

14 

 Auxiliary 

Device 

 

15 

Front Panel 

 

 Features 

 

16 

 Display 

Mode 

 

17 

 

Menu Navigation  

 

18 

 Setpoints 

Menu 

 

19

 

 

Installation  

 

 Terminal 

Layout 

 

20

 External 

Connections 

 

21 

 Communication 

 

23 

 Peer-To-Peer 

Network 

 

25 

 

RS485 Modbus Network 

 

26 

Setup & Tuning  

 

 

Boiler Configuration Menu 

 

28 

 

System Configuration Menu 

 

29 

 Setup 

Menu 

 

30 

 Manual 

Mode 

 

35 

Trouble Shooting 

 

 Alarm 

Messages 

 

36 

 Diagnostics 

Menu 

 

 

38 

 

Sensor Temperature vs. Resistance 

 

41 

 Security 

Menu 

 

42 

Specifications  

 

 

 General 

43 

 

Component Description & Repair Part Numbers  44 

Appendix  
 

A.  Parameter Summary 

45 

 

B. Customer Parameter Worksheet 

47 

 
 

Application 

The Thermal Solutions Boiler Control™ (TSBC™) has 
been designed for commercial hot water boiler 
applications. 
 

Intent 

This instruction manual includes detailed functional, 
installation and setup information.  The intended users 
are application engineers, I&O manual and brochure 
writers, development and specifying engineers and 
installing contractors.   
 
Material from this instruction manual is intended to be 
inserted into individual boiler operation manuals, 
supervisor instruction manuals, brochures and 
promotional and training materials. 
 

IMPORTANT:  THESE INSTRUCTIONS SHOULD BE 
USED IN CONJUNCTION WITH THE 
APPROPRIATE BOILER OR WATER HEATER 
INSTALLATION MANUAL

 
 

 

 
 

TSBC™ Front Panel 

(Showing Power & Alarm LEDs,  

2 Line 16 Character Message Display  

and 4 Pushbuttons) 

Содержание Boiler Control TSBC

Страница 1: ...nce 41 Security Menu 42 Specifications General 43 Component Description Repair Part Numbers 44 Appendix A Parameter Summary 45 B Customer Parameter Worksheet 47 Application The Thermal Solutions Boiler Control TSBC has been designed for commercial hot water boiler applications Intent This instruction manual includes detailed functional installation and setup information The intended users are appl...

Страница 2: ...sed on Setpoints Based on Setpoints Based on Setpoints Based on Setpoints Input RO or Modbus Manually Set Modulation Rate Internal Boiler Control Based on Setpoint Based on Setpoint Based on Setpoint Based on Setpoint Ignored Ignored Lead Boiler Control Peer to Peer Connected With Peer to Peer Connected With Peer to Peer Connected With Peer to Peer Connected Ignored Ignored Remote EMS Control Igno...

Страница 3: ...re Switches HL High Limit Aquastat HP High Pressure Gas Switch IN Boiler Inlet Water Temperature LC Low Water Cutoff Switch LL Lead Lag LO Lockout Indicator LR Local Remote M Electric Motor Mix 3 Way Mixing Valve OA Outside Air Temperature OL Operating Limit Aquastat OO Burner On Off Switch OUT Boiler Outlet Water Temperature RO Remote On Off RST Remote System Temperature SH Space Heating Demand S...

Страница 4: ...sor failure the TSBC will automatically switch to boiler outlet temperature sensor based control Outdoor Air Reset When selected the modulation rate setpoint is automatically adjusted based on outside air temperature Outdoor air reset setpoint saves fuel by adjusting the water temperature of a heating boiler lower as the outside air temperature increases Warm Weather Shutdown WWSD Some boilers are...

Страница 5: ...TSBC Instruction Manual Page 5 of 48 Introduction Overview Thermal Solutions Boiler Control ...

Страница 6: ...stem Pump is On when the System Pump is set to yes and WWSD is set to either WWSD of Boiler or Off d Boiler pump is On during Prepurge and Post Purge when Boiler Pump is set to Purge or boiler is lead Boiler Pump is set to On Lead e Combustion Air Damper Spare Output is maintained On for 2 minutes after the Call For Heat is removed f Modulation rate is held at purge when low fire input is not prov...

Страница 7: ... MODE LCD Display Description Pump Purge Any Mode Except Manual Mode Once a Call For Heat is initiated and Boiler Pump Purge is selected the pump output is energized until the Pump Prepurge Time is complete If the Call For Heat condition still exists at the end of the Prepurge Time the temperature of the water at the sensor may rise with boiler water flowing passed it the pump will continue to ope...

Страница 8: ...en water temperature is above the setpoint by more than the Off Point differential for longer than the Boiler Off Delay parameter Lead Boiler Stop The last boiler remains on line until the water temperature is above the Off Point setpoint for longer than the time delay Notes The Boiler Address parameter assignment determines the boiler sequencing order The Lead Boiler automatically rotates when Ro...

Страница 9: ...e Options Outside Air Reset If enabled the Outside Air Sensor will automatically adjusted the setpoint Warm Weather Shutdown WWSD If enabled the WWSD will disable a boiler start when outside air temperature is above a Warm Weather Shutdown WWSD setpoint Domestic Hot Water Priority DHWP If enabled the DHWP will adjust the setpoint to satisfy the DHWP setpoint when a DHWP input DP is energized Selec...

Страница 10: ... is activated a Call for Heat is also initiated when the Lead boiler modulation rate is above an adjustable High Fire Rate Limit parameter 37 for too long a time Options Outside Air Reset If enabled the Outside Air Sensor will automatically adjusted the setpoint Warm Weather Shutdown WWSD If enabled the WWSD will disable a boiler start when temperature is above a Warm Weather Shutdown WWSD setpoin...

Страница 11: ... off points and boiler outlet temperature Options Warm Weather Shutdown WWSD If enabled the WWSD will disable a boiler start when temperature is above a Warm Weather Shutdown WWSD setpoint Outside Air Temperature may be displayed only Outside Air Reset and Domestic Hot Water Priority input DP are ignored Selecting This Control Mode To select Outlet Sensor Remote SP Mode set the following parameter...

Страница 12: ... determined by setpoint on and off points and Remote System Temperature If a Peer To Peer network is activated a Call for Heat is also initiated when the Lead boiler modulation rate is above an adjustable High Fire Rate Limit Parameter 37 for too long a time Options Warm Weather Shutdown WWSD If enabled the WWSD will disable a boiler start when temperature is above a Warm Weather Shutdown WWSD set...

Страница 13: ...nts are ignored The boiler will turn off if the water temperature increases past the temperature set on the Operational Temperature Limit Options Outside Air Reset and Domestic Hot Water Priority input DP and Warm Weather Shutdown are ignored Selecting This Control Mode To select Remote Control Mode set the following parameters System Configuration Menu Remote Control Remote Mod Remote System Temp...

Страница 14: ...perature increases past the temperature set on the High Temperature Stop parameter Options Outside Air Reset Warm Weather Shutdown and Domestic Hot Water Priority are ignored The Spare Output VI and Combustion Air Damper SO outputs are energized when the operator starts the boiler in manual mode Selecting This Control Mode Manual Mode is activated from the Manual Mode menu when Supervisor password...

Страница 15: ...ed Simply set the Mixing Valve M A parameter to Man and adjust the Mixing Valve as required Once activated the green LED flashes To leave manual mode set the Mixing Valve M A parameter to Auto Combustion Air Damper and Vent Inducer When the Relay CH is closed the Combustion Air Damper CAD and Vent Inducer outputs are energized If the CAD open position is needed to be proven a limit switch may be w...

Страница 16: ... no function in display mode The ENTER key is used to select menus menu items and save edited parameters as follows Select Mode steady text Press ENTER to change into Edit Mode or select a menu or menu item Edit Mode blinking text Press ENTER to save the current value Press MENU to cancel the current editing operation UP DOWN Select Mode steady text Press UP DOWN to change the selected display and...

Страница 17: ...en Remote Sensor Control SP Active Setpoint MOD RATE Modulation Rate SH Space Heating active when DH is not DH Domestic Hot Water Priority visible when DHWP Yes and DP input is true In Boiler Inlet Temperature SP Min In H2O Temp MIX VALVE Modulation Rate Control Mode Outlet Sensor Local SP Mode message shown refer to page 2 for an overview of each control mode LEAD BOILER 0 8 Lead Boiler when zero...

Страница 18: ...4 Setpoints Menu Operational On Off Min Max Setpoints Editable Values refer to page 19 Communication Menu Modbus and Peer To Peer Network Selections refer to pages 23 24 Diagnostic Menu Fault and Low Inlet Temp history Input Output Status refer to pages 38 through 40 System Menu Software revision parameter code and sensor calibration refer to page 40 Security Menu Supervisor and Factory access ref...

Страница 19: ...nput DP closes and DHWP parameter is set to yes and Local SP Mode is selected When the contact is closed the boiler outlet is maintained at or above the DHW Setpoint 75 40 to 90 F WWSD Setpoint The Warm Weather Shutdown WWSD Setpoint used to disable boiler and or system pump operation when enabled by setting the WWSD parameter to WWSD of Boiler WWSD of Sys Pump or Both 76 140 F to 230 F Max SP The...

Страница 20: ...er 5 Vdc Common Boiler Inlet Temperature Boiler Peer To Peer Communication Network V V P P GP WF HL Power Common 24 Vac Power Supply 24 Vac Flame Safeguard Alarm 24 Vac Fuel Valve Energized 24 Vac P P Firing Rate Demand 0 10 Vdc PWM V V Firing Rate Demand 0 10 Vdc OO Burner On Off Switch WF Low Water Flow Switch GP Gas Pressure Switch HL Operating or High Limit CA Low Combustion Air Flow Thermal S...

Страница 21: ...ownstream of all boiler connections Locate the sensor a minimum distance of 10 straight pipe diameters from the flow disturbing fittings Outdoor Air Temperature Sensor Mount the temperature sensor on an outside wall out of direct sunlight preferably on a north facing wall Do not mount sensor near exhaust of any kind as this may affect readings ...

Страница 22: ...the Outside Air and Remote System Temperature sensors should use low impedance shielded twisted pair wire and go directly to the terminals on any one boiler Signal wiring should not be run in the same conduit with power wiring Wire shields may be connected to the common terminal C located on the same terminal block with the outside air and remote system temperature connections 3 The RJ45 sensor ca...

Страница 23: ...re the A represents the active transmission state of the RS485 transmitter as opposed to the line idle state You need only to wire to one of the A terminals and one of the B terminals Phone cable signals 4 wire connect to pin black or yellow and red or green Wire Color Slot Number Connection Black 1 A Red 2 B Green 3 B Yellow 4 A Notes 1 Use standard phone cables although ones that have all six wi...

Страница 24: ...uals Modbus 93 Odd Even None Parity Only visible when Protocol equals Modbus 94 1 120 Seconds Timeout Only visible when Protocol equals Modbus 95 Messages Rcvd Diagnostic tool used to confirm wiring and Modbus master configuration Only visible when Protocol equals Modbus 96 Messages Sent Diagnostic tool used to confirm wiring and Modbus master configuration Only visible when Protocol equals Modbus...

Страница 25: ... all boilers a unique Boiler Address between 1 and 8 and set the Protocol to Peer to Peer 2 Connect all boilers using a RJ11 ended telephone cable 3 Configure all Network Relevant parameters identically on all boilers Unexpected boiler behavior may result if these parameter values differ among boilers on the network When Network Relevant parameters are identical the Param Code parameter will be id...

Страница 26: ...gized Off On 00013 Flame Safeguard Alarm Off On 00014 Call For Heat CFH Off On 00015 General Alarm Off On 4 00016 Vent Inducer Off On 00017 Boiler Pump Off On 00018 System Pump Off On 00019 Spare Output Programmable Off On 00020 State Boiler Disabled Off On 3 00021 State Weather Shutdown Off On 3 00022 State Lockout Off On 3 00023 State Pump Purge Off On 3 00024 State Limit Hold Off On 3 00025 Sta...

Страница 27: ... monitor or control the boilers the Comm Failure alarm is not cleared until a successful write to both the Remote On Off Modbus Command 00004 and Remote Firing Rate or Remote Setpoint 40006 points have been completed power is cycled or the Protocol parameter is changed from Modbus to Peer to Peer and back again 2 The limit string points 00006 00011 are only monitored when there is a Call For Heat ...

Страница 28: ...ute month day year Set Time Date Displays and sets the time and date of the boiler s real time clock 8 No Yes Fuel Limit Specifies a Fuel Limit such as high and low fuel gas pressure switches are connected to input GP Enables Fuel Limit Hold and alarm messages 9 Off Sys Pump Feedback Low Fire Spare Input Sets the function of the Spare Input Terminal SI Off Ignore Sys Pump Feedback Input SI should ...

Страница 29: ...range Modbus SP RS485 Modbus 40006 is used as the temperature setpoint Remote Mod Remote Input C C is used as the modulation rate Modbus Mod RS485 Modbus 40006 is used as the modulation rate 22 60 F to 140 F Remote 1 0 Volt Sets the temperature corresponding to input C C 1Volts Voltage below 1V is considered invalid failed or incorrect wired sensor 23 150 F to 220 F Remote 9 0 Volt Sets the temper...

Страница 30: ...emperature and modulation rate swings 35 1 to 30 Minutes FR On Delay Time Delay after the modulation rate is above the LL Start Trigger before starting the next boiler Long time delay to avoid temperature going below setpoint as a result of a slow process change 36 1 to 30 Minutes FR Off Delay Time Delay after the modulation rate is below the LL Stop Trigger before stopping the next boiler Long ti...

Страница 31: ...d on the following page 49 0 to 100 Full Scale Blower Spd High Linkage Max Position Percent of 0 10 Vdc output V V output that represents a 100 modulation rate This scaling factor allows the TSBC to display 100 when the linkage is at rated boiler output Please Note The Burner input rate adjustment must be completed before this parameter can be set After maximum boiler firing rate is established th...

Страница 32: ...or temperature Display Outside Air Temperature Outdoor Reset Calculate the temperature setpoint based on outdoor temperature using a reset curve defined by Outdoor Set Up Boiler Set Up Outdoor Design and Boiler Design parameters 45 40 F to 100 F Outdoor Set Up The Outdoor Set Up temperature is the outdoor temperature at which the Boiler Set Up temperature is supplied 46 140 F to 180 F Boiler Set U...

Страница 33: ...ure sensor control Modes A smaller value makes the Integral ramp in less time i e faster Integral is a secondary PID modulation rate tuning adjustment that ramps the output over time typically minutes Based on the selected Local PID P select the corresponding from above table Integral value Repeats per minute between 0 5 and 2 0 are typical The burner modulation rate can oscillate if the Integral ...

Страница 34: ... selected Mixing Valve P select the corresponding from table on previous page Integral value The mixing valve can oscillate if the Integral time is too small 63 0 to 10000 Mixing Valve D The Derivative gain value for boiler inlet temperature sensor control mode A larger Derivative gain value produces a larger PID output contribution proportional to the rate of change of the error Setpoint Boiler I...

Страница 35: ...ate Sets the modulation rate to be used for boiler when in Manual Mode Activated only when in Supervisor Mode and Boiler Man Auto Man 103 On Off Boiler On Off Sets the boiler start stop status when in Manual Mode No Turn off boiler if running otherwise remain off Yes Turn on boiler if off otherwise remain on Activated only when in Supervisor Mode and Boiler Man Auto Man 104 Man Auto Mixing Valve M...

Страница 36: ...receive power and the Call For Heat output CH is powered the High Temp Limit Message is displayed Low Air Flow Flashing Red Alarm Light Check combustion air blower and air pressure switch settings and wiring Low Air Flow or Blocked Vent Switch Not Made The air flow and blocked vent switch when provided is preventing a boiler start If terminal CA does not receive power and the Call For Heat output ...

Страница 37: ...nd a successful writes to both the Remote On Off Modbus Command 00004 and Remote Firing Rate or Remote Setpoint 40006 points have been completed power is cycled or the protocol parameter is changed to Peer To Peer and then back to Modbus When a Peer To Peer network has failed the boilers begin operation as stand alone boilers using the selected parameters After a Peer To Peer communication failure...

Страница 38: ...red in memory Each time the boiler inlet temperature is less than the Min In H2O Temp parameter a low temperature event is recorded The BIT History screen automatically toggles between the lowest temperature for the event and Duration Below Setpoint displays and provides time and date of each event SYSTEM Items provided by this menu are shown on page 40 DISCRETE INPUTS These screens provide a conv...

Страница 39: ...Discrete Output ANALOG INPUTS These screens provide a convenient way to trouble shoot wiring during the installation phase Each screen provides the status of a controller analog input These displays show the status of the corresponding Analog Input ANALOG OUTPUTS These screens provide a convenient way to trouble shoot wiring during the installation phase Each screen provides the status of a contro...

Страница 40: ...ory calibrated However it may become necessary to field calibrate due to measuring errors resulting from long wire lengths or third party sensor use This is a single point calibration tool To gain the greatest benefit it is recommended to calibrate as close as possible to the expected operating temperature and measure the temperature at the sensor location Remote System Temperature RST Outside Air...

Страница 41: ...1 212 10 14 55 301 27 80 9 298 82 180 1 169 9 16 52 069 28 82 8 862 83 182 1 129 8 18 49 047 29 84 8 448 84 184 1 089 7 20 46 220 30 86 8 056 86 186 1 052 6 22 43 574 31 88 7 685 87 188 1 016 4 24 41 097 32 90 7 333 88 190 981 2 3 26 38 776 33 92 6 999 89 192 947 9 2 28 36 601 34 94 6 682 90 194 915 9 1 30 34 562 36 96 6 382 91 196 885 2 0 32 32 650 37 98 6 097 92 198 855 7 1 34 30 856 38 100 5 82...

Страница 42: ...er Password parameter The Factory Access Level can be reached by entering the factory password in the Enter Password parameter and holding the Enter key for at least two seconds when accepting the value entered The display will jump to the Access Level parameter menu when the system has entered the Factory Access Level Note that the Access Level parameters value will indicate Supervisor To exit ei...

Страница 43: ...d Low Gas Pressure Switches 24 Vac 1mA HL Operating or High Limit 24 Vac 1mA CA Low Combustion Air Flow 24 Vac 1mA CS Fuel Valve Energized 24 Vac 1mA AL Flame Safeguard Alarm 24 Vac 1mA Discrete Outputs Terminal Description Rating CH Call For Heat CFH 24 Vac 10A LO Lockout Indicator 12 Vdc 100mA VI Spare Output 12 Vdc 100mA BP Boiler Pump 12 Vdc 100mA SP System Pump 12 Vdc 100mA SO Spare Output Pr...

Страница 44: ...tery is NOT used to retain this memory The battery is located at the back of the TSBC for easy replacement Component Description Repair Part Number 1 Thermal Solutions Boiler Control Assembly 101171 03 Individual boiler operating and modulation rate control and modulating lead lag controller Built to UL and CSA standards 2 Replacement Fuse Busman GMC 5A 3 Immersion Temperature Sensor 101935 01 NPT...

Страница 45: ...t Trigger 50 to100 of Modulation Rate Supervisor 30 Yes LL Stop Trigger 0 to 50 of Modulation Rate Supervisor 30 Yes Boiler On Delay 0 to 900 seconds Supervisor 30 Yes Boiler Off Delay 0 to 900 seconds Supervisor 30 Yes FR On Delay 1 to 30 minutes Factory 30 Yes FR Off Delay 1 to 30 minutes Factory 30 Yes High Fire Limit 40 100 Modulation Rate Supervisor 30 Yes Deg Min Hold Off 1 10 Degrees Minute...

Страница 46: ...F Basic 19 Yes Off Point 0 F to 99 F Basic 19 Yes High Temp Stop 60 F to 230 F Basic 19 Yes DHWP setpoint 140 F to 230 F Basic 19 Yes WWSD setpoint 40 F 90 F Basic 19 Yes Max SP 140 F to 230 F Supervisor 19 Yes Min SP 60 F to 230 F Supervisor 19 Yes Min BIT 110 F to 235 F Factory 19 Update Min Inlet H2O Temp 110 F to 180 F Supervisor 19 Update Max H2O Delta T 20F to 50 F Supervisor 19 Update Max D...

Страница 47: ...ntrol Circle one No Remote SP Modbus SP Remote Mod Modbus Mod Remote 1 volts F Remote 9 volts F Remote Sensor Circle one No Display Only Control System Pump Circle one Yes No LWC or CAD Circle one Yes No Alarm Message Setup Menu WWSD Circle one Off WWSD of Boiler WWSD of Sys Pump Both LL Start Trigger LL Stop Trigger Boiler On Delay Seconds Boiler Off Delay Seconds High Fire Limit Rotation Circle ...

Страница 48: ...rational Setpoint F On point F Off Point F High Temp Stop F DHWP setpoint F WWSD setpoint F Max SP F Min SP F Min Inlet H2O Temp F Max H2O Delta T F Max Delta T Hold F Communication Menu Protocol Circle one Peer to Peer Modbus Modbus Address Baud Rate Circle one 9 6 19 2 38 4 Parity Circle one Odd Even None Timeout Seconds Boiler Address ...

Отзывы: