Chapter 4: Programming
92
Phason
on page 142 when setting up alarms. The
worksheet contains descriptions of each setting.
To program alarm settings
1.
From the Main Menu, select
Settings
(1).
2.
From the Settings menu, select
Alarms
(6).
The display should look like the following example.
3.
on page 142. Scroll to a line that needs changing and then
press
ENTER
.
To toggle between
Disabled
and
Enabled
or between
No
and
Yes
, press
+
or
–
and then press
ENTER
.
To enter a number for temperature or duration use the keypad, or press
+
or
–
to adjust the
number and then press
ENTER
.
ALARMS
Probe 1
Disabled
Probe 2
Disabled
Probe 3
Disabled
A
bias temperature
of 5°F allowed so that the room temperature can rise to 85°F before an alarm occurs.
The room temperature exceeds the normal alarm temperature. No alarm occurs because the room temperature is lower than
the
high temperature alarm
plus the
alarm bias
.
A high temperature alarm occurs because the room temperature exceeds the
high temperature alarm
plus the
alarm bias
.
The alarm condition ends when the room temperature drops below the
alarm bias
.
A
B
C
D
Outdoor temperature
Room temperature
A
High temperature alarm
set point (80°F)
B
C
D
Bias time
(duration)
E
After the outdoor temperature drops below the
high temperature alarm
, the bias remains for the duration of the
bias time
.
This gives the room a chance to cool off before removing the bias.