Appendix F: Settings worksheets
21040012
131
Appendix F: Settings worksheets
This appendix contains worksheets for you to use when programming the Supra settings. Each
worksheet contains a brief explanation of the information required. For more information about
Group set point worksheet
A
group set point
is the desired or target temperature for a zone. The
individual set points
for each
variable and relay stage will be adjusted relative to the
group set point
for that zone. Make sure you
set the
group set point
before
setting the
individual set points
.
For example, say the
group set point
for zone 1 is 80°F, a variable-stage fan
set point
is 5 degrees
higher (85°F), and a single-stage heater
set point
is 7 degrees lower (73°F). If you lower the
group
set point
to by 5 degrees to 75°F, the
set points
for the fan and heater will also be lowered by 5
degrees to 80°F and 68°F respectively.
Zone
Temperature
1
(°C / °F)
2
(°C / °F)
3
(°C / °F)
4
(°C / °F)
Tunnel mode worksheet
When the zone temperature is at or above the
tunnel mode set point
, variable stages and relays that
are configured for tunnel mode react as follows.
Actuators
– move to position zero (close the inlet)
Curtains
– close the curtain
Cool relays
and
temperature-based duty cycles
– switch
off the relay
Variable stages
– set the speed to 0%
For more information about enabling tunnel mode for variable stages and relays, read
starting on page 46.
Zone
Temperature
1
(°C / °F)
2
(°C / °F)
3
(°C / °F)
4
(°C / °F)