Appendix E: Configuration worksheets
130
Phason
Warnings worksheet
Warnings are one of the Supra’s built-in diagnostic tools. They warn you about conflicts or out-of-
range conditions as you are programming the control. When the Supra comes from the factory, all
warnings are set to “Yes”.
Warning
Enable?
Description
H/C conflict
Yes No
There is a heat/cool set point conflict
–
The set point for any fixed or
variable heater stage is above the set point for any fixed or variable cool
stage.
Min Ventilation
Yes No
The idle band too small
–
The idle temperature band for any variable cool
stage is less than 10°F.
Large VAR Range
Yes No
The differential for a variable stage is more than 5°.
Odd Timed Events
Yes No
There is an odd number of timed events
–
The number of timed events for
any relay stage is not a multiple of two. Timed events must have an ON
event for every OFF event.
Overlap Events
Yes No
There are overlapping timed events
–
A device has two or more
consecutive ON events, or consecutive OFF events.
Edit aborted
Yes No
You did not press
ENTER
after changing the settings.