background image

THD SERIES S11-S27 HEAVY DUTY ACTUATORS 

Installation & Maintenance Manual 

 

 

September 25, 2015 

www.atcontrols.com 

documents\products\IOM\IOM8036 

 

THD-SERIES S11DA280 THRU S27DA1020 & S11SR280 THRU S27SR1020 DOUBLE ACTING & 

SPRING RETURN SCOTCH YOKE ACTUATORS 

 

INTRODUCTION 

 

A-T Controls THD scotch yoke actuators have been 

designed and engineered to provide high cycle-life to meet the 
demands of our customers.  The actuators are equipped with 
dual travel stops and accessory mounting.   

 

!!!WARNING!!! 

 
FOR YOUR SAFETY, 

IT IS IMPORTANT THAT BEFORE      

REMOVING ANY COMPONENTS OF THE ACTUATOR,  
ENSURE THAT ALL PNEUMATIC AND ELECTRICAL 
SUPPLIES ARE DISCONNECTED AND LOCKOUT AND  
TAGOUT PROCEDURES ARE IMPLEMENTED. PLEASE 
CONSULT FACTORY IF YOU HAVE ANY QUESTIONS 
ON ANY OF THE PROCEDURES LISTED BELOW. 
 

 

1. Installation of Actuator

 

Triac actuators are adapted to the valve by means of an 
intermediate bracket and coupler.  The coupler adapts the 
output of the actuator to the valve shaft.  Standard mounting 
kits provide for mounting the actuator in the direction of the 
pipe. If different orientations are required please consult the 
factory when the order is placed. 
 
Before mounting the actuator on the valve insure that both 
units are in the proper orientation, i.e. both units open or 
closed. Make sure the coupler fits into the actuator and onto 
the valve before assembly. Also check the bracket for proper 
fit.  After mounting the actuator, it may be necessary to adjust 
the travel stops for proper open and closed valve position. 
Always consult the manufactures installation manual for 
specific details before proceeding.   Pneumatically stroke the 
actuator several times to assure smooth proper operation...  

 

2. Air Supply 

Pneumatic piping to the actuator and associated accessories 
should follow the best practices for instrument pneumatic 
piping systems, I.E. lines free of water, oil, pipe sealant or 
other contaminants.  The operating medium is to be filtered 
dry air or inert gas which is filtered to 50 micron particles size 
or less.  It is extremely important that the actuator be powered 
with the proper air pressure and air volume.  Maximum 
working pressure is 100 PSI. Consult the THD series catalog 
for a complete listing of MOP (maximum operating pressure) 
and MAWP (Maximum Allowable Working Pressure) 
Spring return actuators are vented to the atmosphere through 
the front flange.  The Pressure Cylinder must be purged if a 
corrosive atmosphere exists.  Please contact Triac Controls for 
possible solutions if this condition exists. 
 

3. Lubrication

 

Triac actuators are factory lubricated for life and additional 
lubrication is not normally required.  However, for actuators 
performing 100,000 cycles or more, an oil mist lubricator is 
recommended.  Oil mist lubrication requires a mineral oil type 
ISO VG32 Class 1 for usage in temperature range 15 to 158 
Deg. F.  Oil mist lubricator must be set to the lowest setting.  
Once begun, the oil mist lubrication cannot be discontinued. 

CAUTION 

If the actuator is equipped with a pneumatic positioner or 
pneumatic controller, oil mist lubricated air cannot be used 
unless the instrument manufacturer indicates that the 
instrument is compatible with lubricated air. 

 

4. Actuators in Storage or infrequently cycled. 

Actuators in storage should be kept dry and protected from 
adverse conditions until installed. Original port protectors must 
be kept in the ports during storage. Actuators must be cycled 
every 90 days in storage or in operation. Actuators that do not 
cycle in 90 days should have a provision to jog the actuator to 
check for operation if a full cycle cannot be achieved.  
 

5. Double Acting Operation

 

Applying air pressure to the CCW Port drives the piston 
toward the front flange which turns the yoke counterclockwise 
when viewed from the accessory

 

side of the actuator. When 

pressure is applied to the CW Port the piston is driven towards 
the end cap which turns the yoke clockwise.  This is shown in 
Figure 1 

TABLE OF CONTENTS

SECTION DESCRIPTION

1

INSTALLATION OF ACTUATOR

2

AIR SUPPLY

3

LUBRICATION

4

STORAGE OF ACTUATORS/ INFREQUENTLY CYCLED

5

DOUBLE ACTING OPERATION

6

SPRING RETURN OPERATION

7

TRAVEL ADJUSTMENT

8

REPLACEMENT OF CYLINDER SEALS

9

CONVERTING FROM DOUBLE ACTING  
TO SPRING RETURN

10

CONVERTING FROM FAIL CLOSED TO FAIL OPEN

11

SEAL KIT  AND REPAIR PARTS

12

BILL OF MATERIALS

Содержание THD S11 SERIES

Страница 1: ...owered with the proper air pressure and air volume Maximum working pressure is 100 PSI Consult the THD series catalog for a complete listing of MOP maximum operating pressure and MAWP Maximum Allowable Working Pressure Spring return actuators are vented to the atmosphere through the front flange The Pressure Cylinder must be purged if a corrosive atmosphere exists Please contact Triac Controls for...

Страница 2: ...efore the stop bolt can be turned Next loosen the hex nut and then position the stop bolt in or out to the correct position Use care not to damage the o ring seal Retighten lock nut and replace stop bolt cap COUNTER CLOCKWISE STOP BOLT CLOCKWISE STOP BOLT Figure 3 WARNING FOR YOUR SAFETY IT IS IMPORTANT THAT BEFORE REMOVING ANY COMPONENTS OF THE ACTUATOR ENSURE THAT ALL PNEUMATIC AND ELECTRICAL SU...

Страница 3: ...ston over piston rod and install inner hex nut then keyed tab and outer locknut Then align outer hex nut with locking tab and bend tab into slot 23 Lightly grease piston grooves and install o ring and back up strip 24 Lightly grease cylinder completely on the inside surface and carefully slide over the piston until seated on the adapter 25 Lightly grease the o ring for the end cap and install in t...

Страница 4: ...screw pad 7 Install the spring pusher rod into the spring cartridge 8 Place a light coat of blue permantex on the flange gasket and apply to the actuator 9 Lift Spring Cartridge and slide spring pusher rod into access hole and into hole in the sliding block 10 Install the 4 cap screws and lock washers provided with the spring cartridge 11 Place a light coating of permantex blue on cover gasket and...

Страница 5: ...THD SERIES S11 S27 HEAVY DUTY ACTUATORS Installation Maintenance Manual 5 September 25 2015 www atcontrols com documents products IOM IOM8036 ...

Страница 6: ...THD SERIES S11 S27 HEAVY DUTY ACTUATORS Installation Maintenance Manual 6 September 25 2015 www atcontrols com documents products IOM IOM8036 ...

Страница 7: ...and maintenance of A T Controls products The user should read and understand the installation operation maintenance IOM instructions included with the product and train its employees and contractors in the safe use of A T Controls products in connection with the specific application While the information and specifications contained in this literature are believed to be accurate they are supplied ...

Отзывы: