Stock Ref. 459623B
PIR
Visionex
PIR Controller
Fitting & Wiring Instructions
(Suitable for use with a single Vent-Axia fan up to 600W)
PLEASE RETAIN THESE INSTRUCTIONS WITH THE PRODUCT.
Mains 220-240V
Страница 1: ...tock Ref 459623B PIR Visionex Visionex PIR Controller Fitting Wiring Instructions Suitable for use with a single Vent Axia fan up to 600W PLEASE RETAIN THESE INSTRUCTIONS WITH THE PRODUCT Mains 220 240V ...
Страница 2: ...before making electrical connections The Controller MUST be connected to a 220 240V 50Hz AC single phase mains supply WARNING The Visionex MUST NOT be earthed It is Class II double insulated However if the Visionex is mounted on a metal outlet box the outlet box should be earthed If the fan requires an earth connection then earth continuity must be provided All electrical connections should be mad...
Страница 3: ...ENSURE THAT THE MAINS SUPPLY IS SWITCHED OFF AND ISOLATED Using a small flat bladed screw driver carefully unclip the controller front bezel by releasing the 2 clips located at the bottom of the bezel Fig 1 With the bezel removed you can now adjust the timer Fig 2 The Visionex is factory set to run on for about 15 minutes after occupation of the room has ended TO DECREASE the timer overrun period ...
Страница 4: ...entre by post or personal visit Please ensure that it is adequately packed and accompanied by a letter clearly marked Guarantee Claim stating the nature of the fault and providing evidence of date and source of purchase The guarantee is offered to you as an extra benefit and does not effect your legal rights Fig 3 Example wiring connections Fan on when relay energised by room occupation timed over...