200
Ex.
When channels are divided as following:
• CH1 and CH2: Group 1
• CH3 and CH4: Group 2
*2
This becomes Simultaneous temperature rise in process (1) when the temperature rise starts; however, it becomes
Simultaneous temperature rise not in process (0) before the temperature rise starts.
●
When using the simultaneous temperature rise function, turn on CH
Operation request flag (RY11 to RY14) for the
corresponding channels simultaneously.
●
When the simultaneous temperature rise function is used, the setting change rate limiter cannot be used. (
●
When the operating status is changed from stop to run during a simultaneous temperature rise, the simultaneous
temperature rise function stops working and CH
Auto tuning status (RX20 to RX23) turns off. (No error occurs.)
1
0
0
0
1
0
ON
OFF
CH1 Set value (SV)
Temperature rise completion
times are matched in each group.
Temperature process value (PV)
Time
Group 2
arrival point
CH2 Set value (SV)
CH3 Set value (SV)
CH4 Set value (SV)
Temperature rise start point
Group 1
arrival point
CH1 Simultaneous temperature rise status (RX24)
*2
and
CH2 Simultaneous temperature rise status (RX25)
*2
CH3 Simultaneous temperature rise status (RX26)
*2
and
CH4 Simultaneous temperature rise status (RX27)
*2
CH□ Operation monitor
(RX11 to RX14)
Controlled by the temperature control module
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......