(b) Monitoring area (address: 0500H to 09FFH)
*1
This is the value for when the module power supply is turned off and on or at the remote reset.
*2
This column indicates whether data can be read from or written to the remote buffer memory area through sequence
programs.
R: Reading enabled
W: Writing enabled
*3
Available only when the NZ2GF2B-60TCTT4 is used. With other models, this area is handled as a system area.
*4
(TT) represents NZ2GF2B-60TCTT4. (RT) represents NZ2GF2B-60TCRT4.
Address
(decimal
(hexadecimal))
Target
channel
Setting contents
Default
value
Read/Write
Reference
Temperature input mode
1280 to
1535(500H to
5FFH)
System area
1536 (600H)
All CHs
Cold junction temperature process value
0
R
1537 (601H)
System area
1538 (602H)
All CHs
Control switching monitor
0
R
1539 (603H)
All CHs
Function extension bit monitor
0
R
1540 (604H)
All CHs
Sampling cycle monitor
1
R
1541 to
1567(605H to
61FH)
System area
1568 (620H)
CH1
Decimal point position
0(TT)
1(RT)
R
1569 (621H)
CH2
Decimal point position
0(TT)
1(RT)
R
1570 (622H)
CH3
Decimal point position
0(TT)
1(RT)
R
1571 (623H)
CH4
Decimal point position
0(TT)
1(RT)
R
1572 to
2559(624H to
9FFH)
System area
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......