Moving averaging process to a temperature process value
(PV)
Moving averaging process can be set to a temperature process value (PV). With this function, the fluctuation of
temperature process values (PV) can be reduced in electrically noisy environments or in the environments where
temperature process values (PV) fluctuate greatly. The moving averaging process can be disabled to hasten the
response to the change of temperature process values (PV).
(1) Setting method
Follow the procedure below.
1.
Set "Method selection" to "Param write (Station parameter)".
"CC IE Field Configuration" window
Select the temperature control module from "List of
stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
Set "0: Enable" for "Moving averaging process setting" in "Switch Setting" to use the moving
averaging process. Set "1: Disable" for "Moving averaging process setting" in "Switch Setting"
when not using the moving averaging process.
3.
Set "Method selection" to "Param write" of the control mode to be used.
4.
Set "CH
Moving averaging count setting".
●
When Disable (1) is set for "Moving averaging process setting", the setting value for CH
Number of moving averaging
(address: 10EH, 13EH, 16EH, 19EH) is ignored. When Enable (0) is set for "Moving averaging process setting" and the
value out of the setting range is set to CH
Number of moving averaging (address: 10EH, 13EH, 16EH, 19EH), a write
data error (error code: 0004H) occurs.
●
For the module, the moving averaging process is enabled and the number of moving averaging is 2 times as default.
Change the settings if necessary.
Common
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......