329
APPENDICES
A
Appendix
3 Det
a
ils of
Rem
o
te
Buf
fer Me
mory
A
reas
(17)CH
Number of moving averaging (address: 10EH, 13EH, 16EH, 19EH)
For each channel, set the number of moving averaging to be performed to temperature process values (PV).
For details on the moving averaging process to temperature process values (PV), refer to the following.
This setting is enabled only when Enable (0) is set to Moving averaging process setting (address: 1H. b3). If
Disable (1) is set to Moving averaging process setting (address: 1H. b3), this setting is ignored.
For details on Moving averaging process setting (address: 1H. b3), refer to the following.
(a) Setting range
2 to 10 (times)
(b) Enabling the setting
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
(c) Default value
2 (times) are set in all channels as default values.
(18)CH
Control response parameter (address: 10FH, 13FH, 16FH, 19FH)
In the simple two-degree-of-freedom PID control, select the response speed to the change of the set value (SV)
from the following three levels: Slow, Normal, and Fast.
For details on the simple two-degree-of-freedom, refer to the following.
(a) Setting range
Setting value
Setting
contents
Description
0
Slow
Set Slow when reducing an overshoot and undershoot to the change of the set value (SV). However, the settling time is
the longest of the three settings.
1
Normal
Normal has features between Slow and Fast.
2
Fast
Set Fast when speeding up the response to the change of the set value (SV). However, an overshoot and undershoot is
the largest of the three settings.
Common
Standard
Heating-cooling
Time
Temperature process value (PV)
Set value (SV) 2
Set value (SV) 1
Change
Set value (SV) change point
Fast
Normal
Slow
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......