221
CHAPTER 8 FUNCTIONS
8
8.
3 T
e
mperat
ure Cont
rol
M
ode
(3) Dead band setting in two-position control (three-position control)
Set the dead band in two-position control.
Three-position control can be achieved by setting a dead band area in addition to areas for the manipulated value
for heating (MVh) 100% and the manipulated value for cooling (MVc) 100%.
(4) Setting method
1.
Set "Method selection" to "Param write" of the control mode to be used.
"CC IE Field Configuration" window
Select the temperature control module from "List of
stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
Set "CH
Overlap_dead band setting".
Heating only
(manipulated value for cooling (MVc): 0%)
Cooling only
(manipulated value for heating (MVh): 0%)
Heating
Set value (SV)
Cooling
Temperature
process value (PV)
Temperature to start cooling
100%
0%
-100%
Manipulated value
for heating (MVh): 0%
Manipulated value
for cooling (MVc): 0%
Heating proportional band (Ph): 0
Cooling proportional band (Pc):
No setting required
Integral time (I):
No setting required
Derivative time (D):
No setting required
Input range
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......