92
(4) Connecting and disconnecting the cable
To connect the cable, insert the wire with the cable fixing screw loosened and tighten the screw.
To disconnect the cable, pull out the wire with the cable fixing screw loosened with a flathead screwdriver.
(5) Processing method of the cable terminal
Strip the cable about 10mm from the top.
To use a bar solderless terminal, connect it to the stripped part.
(6) Lists of reference products of the bar solderless terminal
The following table lists the reference products of the bar solderless terminal.
Product
Model
Applicable wire size
Manufacturer
Bar solderless terminal
TE 0.5-10
0.5mm
2
NICHIFU Co., ltd.
TE 0.75-10
0.75mm
2
TE 1.0-10
0.9 to 1.0mm
2
TE 1.5-10
1.25 to 1.5mm
2
Tool dedicated for bar solderless
terminal
NH79
Bar solderless terminal
AI 0.5-10WH
0.5mm
2
PHOENIX CONTACT GmbH & Co. KG
AI 0.75-10GY
0.75mm
2
AI 1-10RD
1.0mm
2
AI 1.5-10BK
1.5mm
2
Tool dedicated for bar solderless
terminal
CRIMPFOX6
Cable
Around 10mm