134
(a) How to execute sensor two-point correction
Follow the instructions below.
*1
Enter the value using devices such as a thermocouple, platinum resistance thermometer, and standard DC voltage
generator, or based on a general resistance value.
*2
When the latch is completed, the temperature process value (PV) is stored in CH
Sensor two-point correction offset
value (measured value) (address: 284H, 288H, 28CH, 290H). (
*3
When the latch is completed, the temperature process value (PV) is stored in CH
Sensor two-point correction gain
value (measured value) (address: 286H, 28AH, 28EH, 292H). (
●
If a write data error (error code: 0007H) occurs during sensor two-point correction, correctly configure the setting for
sensor two-point correction again. (The value set for sensor two-point correction of when an error occurred is not written
in the temperature control module.)
●
To use the value set for sensor two-point correction even after the power is turned off and on, back up the value with the
following method.
• Turn off and on Set value backup instruction (RY15). (
Set Sensor two-point correction function (1H) to
Sensor correction function selection (address: 1E4H).
Turn on Initial data setting request flag (RY9).
Set a temperature process value (PV) to be input
to CH□ Sensor two-point correction gain value
(corrected value) (address: 287H, 28BH, 28FH, 293H).
Check that Initial data setting completed flag
(RX9) is on.
Turn off Initial data setting request flag (RY9).
Enter a correction offset value.
*1
Enter a correction gain value.*
1
Set a temperature process value (PV) to be input
to CH□ Sensor two-point correction offset value
(corrected value) (address: 285H, 289H, 28DH, 291H).
Turn on CH□ Sensor two-point correction offset
latch request (RY28, RY2A, RY2C, RY2E).
Check that CH□ Sensor two-point correction
offset latch completion flag (RX28, RX2A, RX2C,
RX2E) is on.
*2
Turn off CH□ Sensor two-point correction offset
latch request (RY28, RY2A, RY2C, RY2E).
Turn on CH□ Sensor two-point correction gain
latch request (RY29, RY2B, RY2D, RY2F).
Check that CH□ Sensor two-point correction gain
latch completion flag (RX29, RX2B, RX2D, RX2F)
is on.
*3
Turn off CH□ Sensor two-point correction gain
latch request (RY29, RY2B, RY2D, RY2F).
1
Set Monitor (1) to CH□ Stop mode setting
(address: 118H, 148H, 178H, 1A8H).
Setting start
Stop the operation.
2
End
Is the ERR.LED off?
Go back to 1 or 2.
YES
NO
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......