256
(2) Programming condition
• The program using the peak current suppression function is designed to suppress the peak current by
automatically changing the values of the upper limit output limiter of CH1 to CH4 and dividing the timing of
the transistor output into four timing.
• The program using the simultaneous temperature rise function is designed to classify the CH1 and CH2 into
group 1 and CH3 and CH4 into group 2 so that the channels in each group reach the set values (SV)
simultaneously.
(3) Contents of the initial setting
(a) Station-based parameter
Set the initial values for the parameters other than the above.
(b) Standard control mode parameter
Setting item
Set value
Control mode switching
0: Standard control
Function extension and sampling cycle
selection
Sampling cycle selection
1: 250ms/4 Channel
Setting item
Set value
CH1 Basic setting
CH1 Input range
2: K: 0 to 1300
(in
increments of 1
)
CH1 Target value_SV_setting
200 (200
)
CH1 Control output cycle setting_CH1 Heating control output cycle setting
20 (20s)
CH2 Basic setting
CH2 Input range
2: K: 0 to 1300
(in
increments of 1
)
CH2 Target value_SV_setting
250 (250
)
CH2 Control output cycle setting_CH2 Heating control output cycle setting
20 (20s)
CH3 Basic setting
CH3 Input range
2: K: 0 to 1300
(in
increments of 1
)
CH3 Target value_SV_setting
300 (300
)
CH3 Control output cycle setting_CH3 Heating control output cycle setting
20 (20s)
CH4 Basic setting
CH4 Input range
2: K: 0 to 1300
(in
increments of 1
)
CH4 Target value_SV_setting
350 (350
)
CH4 Control output cycle setting_CH4 Heating control output cycle setting
20 (20s)
Peak current control function
CH1 Peak current restrain control_divide group setting
1: Group 1
CH2 Peak current restrain control_divide group setting
2: Group 2
CH3 Peak current restrain control_divide group setting
3: Group 3
CH4 Peak current restrain control_divide group setting
4: Group 4
CH1 Warning setting
CH1 Mode setting of warning 1
1: Upper limit input alert
CH1 Warning setting value 1
250 (250
)
CH2 Warning setting
CH2 Mode setting of warning 1
1: Upper limit input alert
CH2 Warning setting value 1
300 (300
)
CH3 Warning setting
CH3 Mode setting of warning 1
1: Upper limit input alert
CH3 Warning setting value 1
350 (350
)
CH4 Warning setting
CH4 Mode setting of warning 1
1: Upper limit input alert
CH4 Warning setting value 1
400 (400
)
CH1 Simultaneous temperature rise
function setting
CH1 Simultaneous temperature rise group setting
1: Group 1
CH1 Simultaneous temperature rise AT mode selection
1: AT for simultaneous
temperature rise
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......