The error details written here are for the case when Error history is A06H to A09H (for Error history 1 (address: A00H to
A0FH)). The following information of when an error has occurred are stored in this area.
• Error occurrence address
• Process value (PV)
• Manipulated value (MV)
• Set value (SV)
For details on Error history, refer to the following.
*2
For the area where data can be written only during the module stop, refer to Lists of Remote Buffer Memory Areas.
*3
If the following values are stored in Error occurrence address, 0 is stored in Process value (PV), Manipulated value
(MV), and Set value (SV) of Error history.
0001H, 0007H, 0080H, 0081H, 01E0H to 01EAH, 1000H
*4
represents the channel number where an error has occurred.
When multiple errors have occurred, only the latest error code is stored in Latest error code (RWr0) or Latest warning code
(RWr2).
The errors that occurred in the past can be checked with the error history of the engineering tool.
For the error history, refer to the following.
• Checking with the command execution of slave station (
• Error history
(address: A00H to FFFH) (
001
H
Moderate error
When either of
CH
Operation
request flag (RY11
to RY14) or CH
Stop request flag
(RY18 to RY1B)
was on, the other
signal was also
turned on.
The operating status
remains same as
before the error
occurrence.
• The process value of the
error channel is stored in
Process value (PV).
• The manipulated value of
the error channel is stored
in Manipulated value (MV).
• The set value of the error
channel is stored in Set
value (SV).
Turn off CH
Operation request flag (RY11
to RY14) or CH
Stop request flag (RY18
to RY1B) of the error channel.
002
H
Moderate error
The value written
to CH
Temperature
process value for
input with another
analog module
(PV) (RWw0 to
RWw3) is invalid.
• The data written is
retained.
• The control is
performed with the
upper/lower limit
value within the
setting range.
• The process value of the
error channel is stored in
Process value (PV).
• The manipulated value of
the error channel is stored
in Manipulated value (MV).
• The set value of the error
channel is stored in Set
value (SV).
Set the value within the setting range to
CH
Temperature process value for input
with another analog module (PV) (RWw0 to
RWw3) of the error channel.
Error
code
(hexadecimal)
Classification
Cause
Operation at error
occurrence
Error details
*1
Action
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......