354
(55)CH
Sensor two-point correction gain value (corrected value) (address: 287H,
28BH, 28FH, 293H)
Set temperature of gain value of the sensor two-point correction.
For details on the sensor two-point correction function, refer to the following.
(a) Setting range
The setting range is identical to the temperature measurement range of the set input range. (
(b) Setting unit
The value to be set differs depending on the stored value in CH
Decimal point position (address: 620H,
621H, 622H, 623H). (
• No decimal place (0): Set a value in 1
(
or digit) unit.
• One decimal place (1): Set a value in 0.1
(
) unit (tenfold value).
(c) Enabling the setting
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
(d) Default value
The default values are set to 0 in all channels.
(56)CH
Auto tuning mode selection (address: 2A0H, 2A2H, 2A4H, 2A6H)
Select the auto tuning mode from the following two modes according to the controlled object to be used.
For details on the auto tuning function, refer to the following.
(a) Setting range
• 0: Standard mode
• 1: High response mode
(b) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(c) Default value
The default values are set to Standard mode (0) in all channels.
Auto tuning mode
Description
Standard mode
The standard mode is appropriate for most controlled objects. This mode is especially suitable for controlled objects that
have an extremely slow response speed or can be affected by noise or disturbance. However, PID constants of slow
response (low gain) may be calculated from controlled objects whose ON time or OFF time in the auto tuning is only
around 10s. In this case, PID constants of fast response can be calculated by selecting the high response mode and
performing the auto tuning.
High response mode
This mode is suitable for controlled objects whose ON time or OFF time in the auto tuning is only around 10s. PID
constants of fast response (high gain) can be calculated. However, the temperature process value (PV) may oscillate near
the set value (SV) because of the too high gain of the PID constants calculated. In this case, select the normal mode and
perform the auto tuning.
Common
Standard
Heating-cooling
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......