(c) ON/OFF timing for CH
Automatic backup setting after auto tuning of PID constants
(address: 119H, 149H, 179H, 1A9H)
The following figure shows ON/OFF timing of this flag for CH
Automatic backup setting after auto tuning of
PID constants (address: 119H, 149H, 179H, 1A9H). (For CH1)
When the data writing to the non-volatile memory is completed normally, CH
Write completion flag (address:
b4 to b7 of 1104H) turns on.
CH
Write completion flag (address: b4 to b7 of 1104H) turns off when CH
Automatic backup setting after
auto tuning of PID constants (address: 119H, 149H, 179H, 1A9H) is set to Disable (0) from Enable (1).
When the data writing to the non-volatile memory fails, CH
Write failure flag (address: b12 to b15 of 1104H)
of the corresponding channel turns on and the temperature control module operates with PID constants
calculated in the previous auto tuning. (The LED status remains.)
CH
Write failure flag (address: b12 to b15 of 1104H) turns off when the data writing of the corresponding
channel is completed normally.
When the data writing fails, perform auto tuning again by turning off and on CH
Auto tuning instruction (RY20
to RY23). If the data writing fails even after executing auto tuning again, a hardware error can be the reason.
Please consult your local Mitsubishi representative.
For details on the ON/OFF timing for CH
Automatic backup setting after auto tuning of PID constants
(address: 119H, 149H, 179H, 1A9H)
●
By referring to this flag at the completion of auto tuning, whether the automatic data backup is completed normally or not
can be checked.
●
After confirming that the following flags are on, set CH
Automatic backup setting after auto tuning of PID constants
(address: 119H, 149H, 179H, 1A9H) to Disable (0).
• CH
Write completion flag (address: b4 to b7 of 1104H) (when automatic data backup is completed normally)
• CH
Write failure flag (address: b12 to b15 of 1104H) (when automatic data backup fails)
If auto tuning is executed under Enable (1), although PID constants are stored after auto tuning is complete, CH
Auto
tuning status (RX20 to RX23) does not turn off.
For details on the auto tuning function, refer to the following.
0
0
0
1
1
OFF
OFF
OFF
ON
ON
ON
Auto tuning completion
(Write failure)
Auto tuning completion
(Write completed)
Controlled by the program
CH1 Automatic backup setting after
auto tuning of PID constants
(address: 119H)
CH1 Write completion flag
(address: b4 of 1104H)
CH1 Write failure flag
(address: b12 of 1104H)
CH1 Auto tuning status (RX20)
Controlled by the temperature control module
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......