365
APPENDICES
A
Appendix
3 Det
a
ils of
Rem
o
te
Buf
fer Me
mory
A
reas
(72)CH
Memory's PID constants read instruction (address: 1100H to 1103H)
PID constants are read from a non-volatile memory and stored in the remote buffer memory by using this
instruction. Setting this remote buffer memory area to Requested (1) stores the value backed up in the non-
volatile memory in the remote buffer memory.
(a) Remote buffer memory areas to store set value of non-volatile memory
The following table lists the remote buffer memory areas whose set value is read.
(b) Setting range
• 0: Not requested
• 1: Requested
(c) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(d) Default value
The default values are set to Not requested (0) in all channels.
(e) Precautions
When Requested (1) is set, do not perform the following operations. An incorrect value may be stored in the
non-volatile memory.
• Change of the set value of the remote buffer memory read from the non-volatile memory by this instruction
(
Page 333, Appendix 3 (23) (d))
• Memory back up (
• Default setting registration (
• Auto tuning (
●
When the parameter is set and auto tuning is carried out, it is recommended that the PID constants should be backed up
to the non-volatile memory after the auto tuning. Turning on this instruction at the next start-up can omits the auto tuning.
●
This instruction is enabled whether the operating status is stop or run. However, the instruction is disabled when CH
Auto tuning instruction (RY20 to RY23) is on. (
Remote buffer memory area name
Remote buffer memory address
Reference
CH1
CH2
CH3
CH4
CH
Proportional band (P) setting
102H
132H
162H
192H
CH
Heating proportional band (Ph)
setting
102H
132H
162H
192H
CH
Cooling proportional band (Pc)
setting
1C4H
1C9H
1CEH
1D3H
CH
Integral time (I) setting
103H
133H
163H
193H
CH
Derivative time (D) setting
104H
134H
164H
194H
CH
Loop disconnection detection
judgment time
116H
146H
176H
1A6H
Standard
Heating-cooling
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......