338
(29)CH
Temperature conversion setting (address: 1C1H to 1C3H)
In the heating-cooling control (normal mode) or the mix control (normal mode), only the temperature
measurement can be performed using temperature input terminals of unused channels.
The following table lists the settable remote buffer memory addresses for each control mode selection.
When the combination of the control mode and the remote buffer memory address is not the setting target in the
above list, the combination is invalid even if it is set.
(a) Setting range
• 0: Not use
• 1: Use
(b) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(c) Default value
The default values are set to Not use (0) in all channels.
●
When CH
Temperature conversion setting (address: 1C1H to 1C3H) is set to Use (1), the temperature conversion
starts. This function does not turn on CH2 to CH4 Operation monitor (RX12 to RX14).
●
When the following control mode is selected, this setting is invalid.
• Standard control
• Heating-cooling control (expanded mode)
• Mix control (expanded mode)
Channel
Control mode
Standard control
Heating-cooling control
(normal mode)
Heating-cooling control
(expanded mode)
Mix control (normal
mode)
Mix control (expanded
mode)
CH1
CH2
1C1H
CH3
1C2H
CH4
1C3H
Heating-cooling
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......