112
Set all the items for the parameter. If any blank exists, the parameter cannot be written to the temperature control module.
10.
Double-click the item to change, and set a new value.
• Items to be set from the pull-down list
Double-click the item to display the pull-down list, and select the value from the list.
• Items to be entered in the text box
Double-click the item and enter a value.
●
When "Control mode switching" is changed and the parameter write is performed, remote buffer memory areas (address
of 100H or later) are overwritten with default values.
●
When "Control output cycle unit switching setting" is changed and the parameter write is performed, the following
parameters are overwritten with default values.
• "Control output cycle setting"
• "Heating control output cycle setting"
• "Cooling control output cycle setting"
●
When "Sampling cycle selection" is changed and the parameter write is performed, remote buffer memory areas
(address of 100H or later) are overwritten with default values.
Setting item
Reference
Function extension and sampling cycle
selection
Auto-setting at input range change
Setting change rate limiter setting
Control output cycle unit switching setting
Moving averaging process setting
Sampling cycle selection
Cyclic data update watch time setting
Control mode switching
HOLD_CLEAR setting
CH
_HOLD_CLEAR setting
Select an item from the pull-down list.
Enter a value in the text box.
The checkbox cannot be unchecked.
The list cannot be collapsed.
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......