328
(16)CH
Primary delay digital filter setting (address: 10DH, 13DH, 16DH, 19DH)
The temperature process values (PV) are smoothed and sudden changes are absorbed by using the primary
delay digital filter.
The time for the temperature process value (PV) to change by 63.3% can be set by the primary delay digital filter
setting (filter setting time).
(a) Setting range
The setting range is 0 or 1 to 100 (1s to 100s). When 0 is set, the primary delay digital filter processing is not
performed.
(b) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(c) Default value
The default value is 0 (the primary delay digital filter is disabled) for all channels.
Common
Time
Time
Temperature
process value (PV)
Temperature
process value (PV)
When the primary delay
digital filter is not set
When the primary delay
digital filter is set
Temperature
process value (PV)
Time
Time
Temperature
process value (PV)
63.3%
When the primary delay
digital filter is not set
When the primary delay
digital filter is set
CH□ Primary delay digital filter setting
(address: 10DH, 13DH, 16DH, 19DH)
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......