101
CHAPTER 6 INSTALLATION AND WIRING
6
6.
6
W
iring of
E
xte
rnal Dev
ic
e
s
and T
e
rm
inal
Bloc
ks
(b) Wiring precautions
To sufficiently exert the function of the temperature control module and improve the system reliability, an
external wiring with less noise interference is required. This section describes wiring precautions.
• Use separate cables from the AC control circuit to the external I/O signals of the temperature control
module to avoid the influence of the AC side surges or induction.
• Do not tie external wires or lay them together with the main circuit lines, high-voltage cables, and load
cables from other than programmable controllers. Provide sufficient distance from a circuit containing high
frequencies, such as high-voltage cables and load main circuits of an inverter. Otherwise, the system
becomes susceptible to noise, surges, or induction.
• Ground the shield wires or shielded cables at one end on the programmable controller side. However,
depending on the external noise condition, it should be grounded on the other side.
• Prevent the adhesion of oil to the terminals and screws. Failure to do so may damage the screw.
• Tighten the terminal screw with an applicable screwdriver. Tightening with an inapplicable screwdriver may
damage the screw.
Terminal No.
Indication
Heating-cooling control (expanded
mode)
Mix control (normal mode)
Mix control (expanded mode)
Symbol
Name
Symbol
Name
Symbol
Name
1
OUT1
L1H
CH1 Heating
output
L1H
CH1 Heating
output
L1H
CH1 Heating
output
2
OUT2
L1C
CH1 Cooling
output
L1C
CH1 Cooling
output
L1C
CH1 Cooling
output
3
OUT3
L2H
CH2 Heating
output
L3
CH3 Output
L3
CH3 Output
4
OUT4
L2C
CH2 Cooling
output
L4
CH4 Output
L4
CH4 Output
5
COM
COM -
Output common
COM -
Output common
COM -
Output common
6
NC
NC
Unused
NC
Unused
NC
Unused
7
IN1 A
CH1 A
CH1 Resistance
thermometer A
CH1 A
CH1 Resistance
thermometer A
CH1 A
CH1 Resistance
thermometer A
8
IN2 A
CH2 A
CH2 Resistance
thermometer A
MT2 A
Monitor 2
Resistance
thermometer A
CH2 A
CH2 Resistance
thermometer A
9
IN1 B
CH1 B
CH1 Resistance
thermometer B
CH1 B
CH1 Resistance
thermometer B
CH1 B
CH1 Resistance
thermometer B
10
IN2 B
CH2 B
CH2 Resistance
thermometer B
MT2 B
Monitor 2
Resistance
thermometer B
CH2 B
CH2 Resistance
thermometer B
11
IN1 b
CH1 b
CH1 Resistance
thermometer b
CH1 b
CH1 Resistance
thermometer b
CH1 b
CH1 Resistance
thermometer b
12
IN2 b
CH2 b
CH2 Resistance
thermometer b
MT2 b
Monitor 2
Resistance
thermometer b
CH2 b
CH2 Resistance
thermometer b
13
IN3 A
CH3 A
CH3 Resistance
thermometer A
CH3 A
CH3 Resistance
thermometer A
CH3 A
CH3 Resistance
thermometer A
14
IN4 A
CH4 A
CH4 Resistance
thermometer A
CH4 A
CH4 Resistance
thermometer A
CH4 A
CH4 Resistance
thermometer A
15
IN3 B
CH3 B
CH3 Resistance
thermometer B
CH3 B
CH3 Resistance
thermometer B
CH3 B
CH3 Resistance
thermometer B
16
IN4 B
CH4 B
CH4 Resistance
thermometer B
CH4 B
CH4 Resistance
thermometer B
CH4 B
CH4 Resistance
thermometer B
17
IN3 b
CH3 b
CH3 Resistance
thermometer b
CH3 b
CH3 Resistance
thermometer b
CH3 b
CH3 Resistance
thermometer b
18
IN4 b
CH4 b
CH4 Resistance
thermometer b
CH4 b
CH4 Resistance
thermometer b
CH4 b
CH4 Resistance
thermometer b
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......