11.5
Unit Test
Execute a unit test to check that the hardware of the temperature control module is normal.
Remark
When unit test fails, the error details can be checked in the error history.
To check the error history, change the station number back from TEST and connect the temperature control module to the
master station with an Ethernet cable.
For the error history, refer to the following.
• Checking with the command execution of slave station (
• Error history
(address: A00H to FFFH) (
1.
Power off the module.
2.
Connect the PORT1 and PORT2 of the temperature
control module with an Ethernet cable.
3.
Set the station number setting switches as follows.
10: TEST
1: 0
4.
Power on the module.
5.
The unit test begins.
The MODE LED flashes while the unit test is being
executed.
6.
The MODE LED turns off when the unit test is
completed.
• When the test is completed, the ERR. LED remains off.
• When the test fails, the ERR. LED turns on. If the test fails,
replace the Ethernet cable and execute the test again. If
the test fails again, the possible cause is a hardware failure
of the temperature control module. Please consult your
local Mitsubishi representative.
Ethernet cable
: Flashing
: Off
: On
When completed
When failed
: Flashing
: On
: Flashing
: On
: Off
: Off
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......