CHAPTER 8 FUNCTIONS
8
8.
1 Com
m
on F
unc
tions
(3) Setting method
1.
Set "Method selection" to "Param write" of the control mode to be used.
"CC IE Field Configuration" window
Select the temperature control module from "List of
stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
Set "1: Enable" for "CH
Measured value_PV_scaling function_enable_disable setting".
3.
Set "CH
Measured value_PV_scaling lower limit value" and "CH
Measured value_PV_scaling
upper limit value".
●
An error does not occur even though the areas above are set as follows: Lower limit value
Upper limit value. The
temperature process value (PV) is scaled according to the formula shown in the following.
●
If a value outside the temperature measurement range is measured, the value set as an upper limit or a lower limit is
stored into the following remote register.
• CH
Process value (PV) scaling value (RWr8 to RWrB) (