222
8.3.24
Temperature conversion function (using unused channels)
In heating-cooling control (normal mode) and mix control (normal mode), only temperature measurement can be
performed by using unused temperature input terminals. When this function is used, temperature control and alert
judgment are not performed.
(1) Temperature input terminals that can be used
Temperature input terminals that can be used for this function differ depending on the control mode.
Use the terminals indicating MT2
(Monitor CH2), MT3
(Monitor CH3), and MT4
(Monitor CH4) in the
following table.
Terminal No.
Terminal symbol
NZ2GF2B-60TCTT4
NZ2GF2B-60TCRT4
Heating-cooling control
(normal mode)
Mix control (normal mode)
Heating-cooling control
(normal mode)
Mix control (normal mode)
1
L1H
L1H
L1H
L1H
2
L1C
L1C
L1C
L1C
3
L2H
L3
L2H
L3
4
L2C
L4
L2C
L4
5
COM -
COM -
COM -
COM -
6
Unused
Unused
Unused
Unused
7
CH1 +
CH1 +
CH1 A
CH1 A
8
CH2 +
MT2 +
CH2 A
MT2 A
9
CH1 -
CH1 -
CH1 B
CH1 B
10
CH2 -
MT2 -
CH2 B
MT2 B
11
Unused
Unused
CH1 b
CH1 b
12
CJ
CJ
CH2 b
MT2 b
13
Unused
Unused
MT3A
CH3 A
14
CJ
CJ
MT4A
CH4 A
15
MT3 +
CH3 +
MT3B
CH3 B
16
MT4 +
CH4 +
MT4B
CH4 B
17
MT3 -
CH3 -
MT3B
CH3 b
18
MT4 -
CH4 -
MT4b
CH4 b
Heating-cooling
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......