246
(2) Programming condition
This program is designed to read the temperatures measured with the thermocouple (K type, 0 to 1300
)
connected to CH1.
An error code can be read and reset.
The self-tuning function automatically sets the PID constants optimal to CH1.
(3) Contents of the initial setting
(a) Station-based parameter
Set the initial values for the parameters other than the above.
(b) Standard control mode parameter
Set the initial values for the parameters other than the above.
*1
This setting is necessary only when the self-tuning function is used.
Setting item
Set value
Control mode switching
0: Standard control
Function extension and sampling cycle
selection
Sampling cycle selection
1: 250ms/4 Channel
Setting item
Set value
CH1 Basic setting
CH1 Input range
2: K: 0 to 1300
(in
increments of 1
)
CH1 Target value_SV_setting
2000 (200
)
CH1 Limiter setting
CH1 Upper limit setting limiter
4000 (400
)
CH1 Lower limit setting limiter
0 (0
)
CH1 Control output cycle setting_CH1 Heating control output cycle setting
30 (30s)
CH1 Warning setting
CH1 Mode setting of warning 1
1: Upper limit input alert
CH1 Warning setting value 1
2500 (250
)
Self tuning setting
CH1 Self tuning setting
1: Starting ST (PID constant
only)
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......