347
APPENDICES
A
Appendix
3 Det
a
ils of
Rem
o
te
Buf
fer Me
mory
A
reas
(b) Setting range
The following table lists set values and setting ranges which are available for alert set values set in each alert
mode.
(c) Enabling the setting
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
When the set value is out of the range, a write data error (error code: 0004H) occurs, and the temperature
control module operates with the previous set value.
(d) Default value
The default values are set to 0 in all channels.
Setting
value
Alert mode
Setting range of alert set value
0
(no alert)
1
Upper limit input alert
Within the temperature measurement range of the set input range
(
2
Lower limit input alert
3
Upper limit deviation alert
(-(full scale)) to full scale
4
Lower limit deviation alert
5
Upper lower limit deviation alert
0 to full scale
6
Within-range alert
7
Upper limit input alert with standby
Within the temperature measurement range of the set input range
(
8
Lower limit input alert with standby
9
Upper limit deviation alert with standby
(-(full scale)) to full scale
10
Lower limit deviation alert with standby
11
Upper lower limit deviation alert with standby
0 to full scale
12
Upper limit deviation alert with standby (second time)
(-(full scale)) to full scale
13
Lower limit deviation alert with standby (second time)
14
Upper lower limit deviation alert with standby (second time)
0 to full scale
15
Upper limit deviation alert (using the set value (SV))
(-(full scale)) to full scale
16
Lower limit deviation alert (using the set value (SV))
17
Upper lower limit deviation alert (using the set value (SV))
0 to full scale
18
Within-range alert (using the set value (SV))
19
Upper limit deviation alert with standby (using the set value (SV))
(-(full scale)) to full scale
20
Lower limit deviation alert with standby (using the set value (SV))
21
Upper lower limit deviation alert with standby (using the set value
(SV))
0 to full scale
22
Upper limit deviation alert with standby (second time) (using the set
value (SV))
(-(full scale)) to full scale
23
Lower limit deviation alert with standby (second time) (using the set
value (SV))
24
Upper lower limit deviation alert with standby (second time) (using
the set value (SV))
0 to full scale
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......