312
(4) HOLD/CLEAR setting (address: 81H)
Make the HOLD/CLEAR setting for control output.
• 0: CLEAR (default)
• Other than 0: HOLD
The following table shows the correspondence between the setting of HOLD/CLEAR setting (address: 81H) and
the operation of the temperature control module in cases when an error of the module occurs, when an error of
the CPU module occurs/the operating status of the CPU module is STOP, and when the communication is
disconnected.
*1
CH
Stop mode setting (address: 118H, 148H, 178H, 1A8H) (
*2
CH
Operation monitor (RX11 to RX14) turns off.
(a) Enabling the setting
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
(5) CH
Input range (address: 100H, 130H, 160H, 190H)
Select the set value according to temperature sensor, temperature measurement range
*1
, output temperature
unit (Celsius (
)/Fahrenheit (
)/digit) and resolution (1/0.1) which are used with the temperature control module.
*1
In the case of input from other analog modules (such as an A/D converter module) also, set these values.
Ex.
When using NZ2GF2B-60TCTT4 and selecting the following thermocouple, set 1 for CH
Input range
(address: 100H, 130H, 160H, 190H).
• Thermocouple type: R
• Temperature measurement range: 0 to 1700
• Resolution: 1
When using NZ2GF2B-60TCTT4, refer to
When using NZ2GF2B-60TCRT4, refer to
Status
Processing
HOLD/CLEAR setting (address: 81H)
CLEAR
HOLD
Error
Temperature control module
write data error
Follow the operation carried out when an error occurs, as described in the error code list.
Temperature control module
hardware error
Depends on the symptom of the hardware
CPU stop error
Stops the operation and turns off external
output
Continues the operation and performs external
output
CPU operation
RUN
STOP
Follows the stop mode setting
Continues the operation and performs external
output
Communication disconnection
Stops the operation and turns off external
output
Continues the operation and performs external
output
Common
b15
b0
b8
b7
b4
b3
b11
b12
CH4
CH3
CH2
CH1
to
to
to
to
Common
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......