315
APPENDICES
A
Appendix
3 Det
a
ils of
Rem
o
te
Buf
fer Me
mory
A
reas
Remark
For the following mode and channel, CH
Input range (address: 100H, 130H, 160H, 190H) cannot be set to 201 to 205. If
these values are set, a write data error (error code: 0004H) occurs.
(b) Setting range of NZ2GF2B-60TCRT4
Set CH
Input range (address: 100H, 130H, 160H, 190H) according to the platinum resistance thermometer
type.
*1
When the input range is changed, the set values in some remote buffer memory areas are initialized automatically and
return to the default value (0). (
*2
Same as the NZ2GF2B-60TCTT4.
Remark
For the following mode and channel, CH
Input range (address: 100H, 130H, 160H, 190H) cannot be set to 201 to 205. If
these values are set, a write data error (error code: 0004H) occurs.
Mode
Corresponding channel
Temperature input mode
CH1 to CH4
Temperature control mode
Heating-cooling control (normal mode)
CH3, CH4
Mix control (normal mode)
CH2
Platinum resistance
thermometer type
Temperature
measurement
range
Celsius (
)
/Fahrenheit
(
)/digit
Resolution
CH
Input range
(address: 100H,
130H, 160H, 190H)
Auto-setting at input range change
CH
Upper limit setting
limiter, CH
Process
alarm upper lower limit
value, CH
Process
alarm upper upper limit
value
CH
Lower limit setting
limiter, CH
Process
alarm lower lower limit
value, CH
Process
alarm lower upper limit
value
Pt100
-200.0 to 600.0
0.1
7 (Default value)
6000
-2000
-200.0 to 200.0
0.1
8
2000
-2000
-200.0 to 850.0
0.1
54
8500
-2000
-300 to 1100
1
141
1100
-300
-300.0 to 300.0
0.1
143
3000
-3000
JPt100
-200.0 to 500.0
0.1
5
5000
-2000
-200.0 to 200.0
0.1
6
2000
-2000
-200.0 to 640.0
0.1
53
6400
-2000
-300 to 900
1
140
900
-300
-300.0 to 300.0
0.1
142
3000
-3000
Input from other analog
modules (0 to 4000)
0 to 4000
digit
1
201
4000
0
Input from other analog
modules (0 to 12000)
0 to 12000
digit
1
202
12000
0
Input from other analog
modules (0 to 16000)
0 to 16000
digit
1
203
16000
0
Input from other analog
modules (0 to 20000)
0 to 20000
digit
1
204
20000
0
Input from other analog
modules (0 to 32000)
0 to 32000
digit
1
205
32000
0
Mode
Corresponding channel
Temperature input mode
CH1 to CH4
Temperature control mode
Heating-cooling control (normal mode)
CH3, CH4
Mix control (normal mode)
CH2
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......