237
CHAPTER 9 PROGRAMMING
9
9.
3 Pr
ogram Ex
amples
(2) Programming condition
This program is designed to read the temperatures measured with the thermocouple (K type, -200.0 to 1300.0
)
connected to CH1 to CH3.
An error code can be read and reset.
The following table lists other programming conditions.
(3) Contents of the initial setting
(a) Station-based parameter
Set the initial values for the parameters other than the above.
(b) Temperature input mode parameter
Set the initial values for the parameters other than the above.
Item
Description
CH1
CH2
CH3
Sampling cycle
250ms
Temperature conversion
method
Sampling processing
Sampling processing
Primary delay digital filter (time constant 1s)
Alert output function
• Process alarm lower lower limit value: 2000
(200.0
)
• Process alarm lower upper limit value: 2050
(205.0
)
• Process alarm upper lower limit value: 2950
(295.0
)
• Process alarm upper upper limit value: 3000
(300.0
)
• Rate alarm warning detection cycle: 4 times (1s)
• Rate alarm upper limit value: 50 (+5.0
)
• Rate alarm lower limit value: -50 (-5.0
)
Setting item
Set value
Control mode switching
100h: Temperature input
mode
Function extension and sampling cycle
selection
Sampling cycle selection
1: 250ms/4 Channel
Setting item
Set value
CH1 Basic setting
CH1 Input range
49: K: -200.0 to 1300.0
(in
increments of 0.1
)
CH2 Basic setting
CH2 Input range
49: K: -200.0 to 1300.0
(in
increments of 0.1
)
CH3 Basic setting
CH3 Input range
49: K: -200.0 to 1300.0
(in
increments of 0.1
)
CH2 Primary delay digital filter setting
2
CH2 Process alarm setting
CH2 Process alarm warning output enable_disable setting
0: Enable
CH2 Process alarm lower lower limit value
2000
CH2 Process alarm lower upper limit value
2050
CH2 Process alarm upper lower limit value
2950
CH2 Process alarm upper upper limit value
3000
CH3 Rate alarm setting
CH3 Rate alarm warning output enable_disable setting
0: Enable
CH3 Rate alarm warning detection cycle
4
CH3 Rate alarm upper limit value
50
CH3 Rate alarm lower limit value
-50
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......