350
(47)CH
Process alarm lower lower limit value (address: 251H, 25AH, 263H, 26CH)
, CH
Process alarm lower upper limit value (address: 252H, 25BH, 264H,
26DH) ,
CH
Process alarm upper lower limit value (address: 253H,
25CH, 265H, 26EH)
, CH
Process alarm upper upper limit value
(address: 254H, 25DH, 266H, 26FH)
Set the lower lower limit value, lower upper limit value, upper lower value, and upper upper limit of process alarm.
(a) Setting range
The setting range should meet the both of the following. If the setting is out of the setting value, out of range
error (error code: 0008H) occurs.
• Within the temperature measurement range of set input range (
• Process alarm lower lower limit value
Process alarm lower upper limit value
Process alarm upper
lower limit value
Process alarm upper upper limit value
(b) Setting unit
The value to be set differs depending on the stored value in CH
Decimal point position (address: 620H,
621H, 622H, 623H). (
• No decimal place (0): Set a value in 1
(
or digit) unit.
• One decimal place (1): Set a value in 0.1
(
) unit (tenfold value).
(c) Enabling the setting
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
(d) Default value
(48)CH
Rate alarm alert output enable/disable setting (address: 255H, 25EH,
267H, 270H)
Set whether to enable or disable alert output of rate alarm. For details on the rate alarm, refer to the following.
(a) Setting range
• 0: Enable
• 1: Disable
(b) Enabling the setting
To enable the setting, turn on and off Initial data setting request flag (RY9) while the operation is stopped.
(c) Default value
The default values are set to Disable (1) in all channels.
Item
Default value
NZ2GF2B-60TCTT4
NZ2GF2B-60TCRT4
CH
Process alarm lower lower limit value
0
-2000
CH
Process alarm lower upper limit value
0
-2000
CH
Process alarm upper lower limit value
1300
6000
CH
Process alarm upper upper limit value
1300
6000
Temperature
Input
Temperature
Input
Temperature
Input
Temperature
Input
Temperature
Input
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......