(6) Items related to control method
The following table shows the setting items related to control method.
*1
When outside the setting range, a write data error (error code: 0004H) occurs.
The temperature control module automatically sets optimum PID constants if the following functions are used.
• Auto tuning function (
• Self-tuning function (
Name
Setting range
Two-position control
P control
PD control
PI control
PID control
CH
Input range
Thermocouple: 1 to 4, 11 to 28, 36 to 48, 49 to 52, 100 to 117, 130 to 132, 201 to 205
Platinum resistance thermometer: 5 to 8, 53, 54, 140 to 143, 201 to 205
CH
Set value (SV) setting
Set a value within the temperature measurement range of the set input range.
CH
Proportional band (P)
setting
Fix the setting to 0.
Set the value within the range of 0 to 10000 (0.0% to 1000.0%) for the full scale of the set input
range.
CH
Heating proportional band
(Ph) setting
CH
Cooling proportional band
(Pc) setting
The setting is
ignored.
Set the value within the range of 1 to 10000 (0.1% to 1000.0%) for the full scale of the set input
range.
CH
Integral time (I) setting
The setting is
ignored.
Fix the setting to 0.
Fix the setting to 0.
1 to 3600 (s)
1 to 3600 (s)
CH
Derivative time (D) setting
The setting is
ignored.
Fix the setting to 0.
1 to 3600 (s)
Fix the setting to 0.
1 to 3600 (s)
CH
Upper limit output limiter
The setting is
ignored.
-50 to 1050 (-5.0% to 105.0%)
CH
Lower limit output limiter
CH
Heating upper limit output
limiter
0 to 1050 (0.0% to 105.0%)
CH
Cooling upper limit output
limiter
CH
Output variation limiter
setting
The setting is
ignored.
1 to 1000 (0.1%/s to 100.0%/s)
CH
Adjustment sensitivity
(dead band) setting
Set the value within
the range 1 to 100
(0.1% to 10.0%) of the
full scale of the set
input range.
The setting is ignored.
CH
Control output cycle
setting
The setting is
ignored.
• When the control output cycle unit selection setting is set to the cycle of 1s: 1 to 100 (1s to 100s)
• When the control output cycle unit selection setting is set to the cycle of 0.1s: 5 to 1000 (0.5s to
100.0s)
CH
Heating control output
cycle setting
CH
Cooling control output
cycle setting
CH
Overlap/dead band
setting
Set the value within the range -100 to 100 (-10.0% to 10.0%) of the full scale of the set input range.
CH
Manual reset amount
setting
The setting is
ignored.
Set the value within the range of -1000 to 1000
(-100.0% to 100.0%) for the full scale of the set
input range.
The setting is ignored.
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......