CHAPTER 8 FUNCTIONS
8
8.
3 T
e
mperat
ure Cont
rol
M
ode
8.3.4
Manual reset function
The position of the stable condition in P control or PD control can be shifted manually using this function.
By shifting the proportional band (P), an offset (remaining deviation) is manually reset.
The offset is reset by determining and setting the amount to shift the value of the manipulated value (MV) in a stable
condition from the reference value.
The reference value is 50% for standard control, and 0% for heating-cooling control.
This function can be active only in P control and PD control. This function is inactive when integral time (I) is other than 0.
CH
Manual reset amount setting (address: 112H, 142H, 172H, 1A2H) is ignored even if it is set. (Note that a write data
error (error code: 0004H) occurs if it is outside the setting range.)
(1) Standard control
The set value (SV) is set where the manipulated value (MV) is 50%. Due to this, as long as the temperature
process value (PV) and the set value (SV) is not in equilibrium at 50% of manipulated value (MV), an offset
(remaining deviation) generates.
When an offset generates, the proportional band (P) can be manually shifted by the amount of the offset
(remaining deviation).
Ex.
The temperature control module shifts the manipulated value (MV) by which the temperature is stabilized
at the set value (SV) from 50% to 80% when the manual reset function is used under the following
conditions.
• Control method: P control
• CH
Manual reset amount setting (address: 112H, 142H, 172H, 1A2H): 300 (30%)
Standard
Heating-cooling
Set value (SV)
100%
0%
50%
Input range
Set values as follows:
Integral time (I): 0
Derivative time (D): 0
Manual reset
Manual reset range: -100.0 to 100.0% (unit: 0.1%)
(Set a value from -1000 to 1000.)
80%
Proportional band
(P)
(Percentage to the full scale)
Manipulated value
(MV)
The manipulated value (MV) is shifted
from 50 to 80% to keep the temperature
stable at the set value (SV).
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......