(2) Remote buffer memory areas related to auto tuning
To execute auto tuning, the following data need to be set in advance. Note that other data must be preset to the
values used for actual operation since actual control starts on completion of auto tuning.
When "0" is set for the proportional band (P)/heating proportional band (Ph), auto tuning is not executed.
(
(3) Storing the calculated value after auto tuning
After auto tuning is completed, the calculated values are stored into the following remote buffer memory areas.
*1
A value twice greater than the one in CH
Integral time (I) setting (address: 103H, 133H, 163H, 193H) is automatically
set. However, if this setting is 0 (s) when auto tuning is in process, the loop disconnection detection judgment time is not
stored.
Remote buffer memory area name
Remote buffer memory address
Reference
CH1
CH2
CH3
CH4
CH
Input range
100H
130H
160H
190H
CH
Set value (SV) setting
101H
131H
161H
191H
CH
Upper limit output limiter
105H
135H
165H
195H
CH
Lower limit output limiter
106H
136H
166H
196H
CH
Heating upper limit output limiter
105H
135H
165H
195H
CH
Cooling upper limit output limiter
1C5H
1CAH
1CFH
1D4H
CH
Output variation limiter setting
107H
137H
167H
197H
CH
Sensor correction value setting
280H
281H
282H
283H
CH
Control output cycle setting
10CH
13CH
16CH
19CH
CH
Heating control output cycle setting
10CH
13CH
16CH
19CH
CH
Cooling control output cycle setting
1C6H
1CBH
1D0H
1D5H
CH
Primary delay digital filter setting
10DH
13DH
16DH
19DH
CH
AUTO/MAN mode shift
113H
143H
173H
1A3H
CH
AT bias setting
2A1H
2A3H
2A5H
2A7H
CH
Forward/reverse action setting
115H
145H
175H
1A5H
CH
Auto tuning mode selection
2A0H
2A2H
2A4H
2A6H
Remote buffer memory area name
Remote buffer memory address
Reference
CH1
CH2
CH3
CH4
CH
Proportional band (P) setting
102H
132H
162H
192H
CH
Heating proportional band (Ph) setting
102H
132H
162H
192H
CH
Cooling proportional band (Pc) setting
1C4H
1C9H
1CEH
1D3H
CH
Integral time (I) setting
103H
133H
163H
193H
CH
Derivative time (D) setting
104H
134H
164H
194H
CH
Loop disconnection detection judgment
time
116H
146H
176H
1A6H
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......